A2HT | High Temperature Industrial Cable Gland For all types of Unarmoured & Braid Armoured Cables

High Temperature, Single Seal Industrial Cable Gland

• -60°C to 180°C high temperature ThermIn seals
• High quality durable materials
• Robust, heavy duty design
• Displacement type seal
• Designed to prevent Coldflow
• Deluge protected

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications * Impact = Level 8, Cable Anchorage = Class B
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Continuous Operating Temperature -60°C to +180°C
Ingress Protection Rating ** IP66, IP67 & IP68***
Deluge Protection Compliance DTS01 : 91
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP Thermoset Rubber
Cable Type Unarmoured + Braided
Sealing Technique CMP Unique Displacement Seal Concept
Sealing Area(s) Cable Outer Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to maintaining a seal for further information.
***IP68 tested to a minimum depth of 30 metres for 12 hours, alternate depths / duration's cab be provided upon request

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Combined Ordering Reference (*Brass Metric)Available Entry Threads 'C' (Alternate Metric Thread Lengths
Available)
Overall Cable DiameterAcross Flats 'D'Across Corners 'D'Protrusion Length 'F'
StandardOption
SizeTypeOrdering SuffixMetricThread Length (Metric) 'E'NPTThread Length (NPT) 'E'NPTMinMaxMaxMaxMax
16A2HT1RAM160.39---0.130.310.941.041.37
16PA2HT1RAM160.39---0.130.310.870.951.37
20S/16A2HT1RAM200.391/2'0.783/4'0.130.310.941.041.30
20S/16PA2HT1RAM200.39---0.130.310.870.951.28
20SA2HT1RAM200.391/2'0.783/4'0.260.440.941.041.37
20SPA2HT1RAM200.39---0.260.440.870.951.35
20A2HT1RAM200.391/2'0.783/4'0.280.531.061.171.45
20PA2HT1RAM200.39---0.280.530.941.041.62
25A2HT1RAM250.393/4'0.801'0.450.771.421.561.70
25PA2HT1RAM250.39---0.450.771.261.391.94
32A2HT1RAM320.391'0.981 1/4'0.751.001.611.781.63
40A2HT1RAM400.591 1/4'1.011 1/2'0.981.271.972.171.54
50SA2HT1RAM500.591 1/2'1.032'1.221.502.172.381.63
50A2HT1RAM500.592'1.062 1/2'1.401.732.362.601.80
63SA2HT1RAM630.592'1.062 1/2'1.631.962.783.061.70
63A2HT1RAM630.592 1/2'1.573'1.902.162.953.251.72
75SA2HT1RAM750.592 1/2'1.573'2.132.443.313.641.79
*For material options add the following suffix to the Ordering Reference; Brass (no suffix required); Nickel Plated Brass ‘5’; 316 Grade Stainless Steel ‘4’; Copper Free Aluminium ‘1’
For NPT options add the following digits to the material suffix; ½” = 31; ¾” = 32; 1” = 33; 1 ¼” = 34; 1 ½” = 35; 2” = 36; 2 ½” = 37; 3” = 38; 3 ½” = 39; 4” = 310 (Brass requires prefix ‘0’)
Examples: 32A2HT1RA534 = Nickel Plated Brass 1¼” NPT, 50SA2HT1RA035 = Brass 1½” NPT, 25A2HT1RA432 = Stainless Steel ¾” NPT, 20A2HT1RA5 = Nickel Plated Brass M20
Dimensions displayed in inches unless otherwise stated
Combined Ordering Reference (*Brass Metric)Available Entry Threads 'C' (Alternate Metric Thread Lengths
Available)
Overall Cable DiameterAcross Flats 'D'Across Corners 'D'Protrusion Length 'F'
StandardOption
SizeTypeOrdering SuffixMetricThread Length (Metric) 'E'NPTThread Length (NPT) 'E'NPTMinMaxMaxMaxMax
16A2HT1RAM1610.0---3.28.024.026.434.9
16PA2HT1RAM1610.0---3.28.022.024.234.7
20S/16A2HT1RAM2010.01/2'19.93/4'3.28.024.026.432.9
20S/16PA2HT1RAM2010.0---3.28.022.024.232.4
20SA2HT1RAM2010.01/2'19.93/4'6.511.224.026.434.9
20SPA2HT1RAM2010.0---6.511.222.024.234.4
20A2HT1RAM2010.01/2'19.93/4'7.013.527.029.736.8
20PA2HT1RAM2010.0---7.013.524.026.441.1
25A2HT1RAM2510.03/4'20.21'11.519.536.039.643.1
25PA2HT1RAM2510.0---11.519.532.035.249.4
32A2HT1RAM3210.01'25.01 1/4'19.025.541.045.141.5
40A2HT1RAM4015.01 1/4'25.61 1/2'25.032.250.055.039.1
50SA2HT1RAM5015.01 1/2'26.12'31.038.255.060.541.4
50A2HT1RAM5015.02'26.92 1/2'35.644.060.066.045.8
63SA2HT1RAM6315.02'26.92 1/2'41.549.970.577.643.3
63A2HT1RAM6315.02 1/2'39.93'48.254.975.082.543.6
75SA2HT1RAM7515.02 1/2'39.93'54.061.984.092.445.4
*For material options add the following suffix to the Ordering Reference; Brass (no suffix required); Nickel Plated Brass ‘5’; 316 Grade Stainless Steel ‘4’; Copper Free Aluminium ‘1’
For NPT options add the following digits to the material suffix; ½” = 31; ¾” = 32; 1” = 33; 1 ¼” = 34; 1 ½” = 35; 2” = 36; 2 ½” = 37; 3” = 38; 3 ½” = 39; 4” = 310 (Brass requires prefix ‘0’)
Examples: 32A2HT1RA534 = Nickel Plated Brass 1¼” NPT, 50SA2HT1RA035 = Brass 1½” NPT, 25A2HT1RA432 = Stainless Steel ¾” NPT, 20A2HT1RA5 = Nickel Plated Brass M20
Dimensions displayed in millimeters unless otherwise stated

Technical Illustration

Additional Information

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now