Product Finder

Product Finder

Our Product Finder tool allows you to find the perfect product for your requirements.

PX2K | Ex e, Ex d, Ex nR, Ex ta | Explosive Atmosphere Barrier Cable Gland For all types of Armoured cables

Globally Approved, Explosive Atmosphere Barrier Cable Gland

• Metal-to-metal armour clamping
• Direct & remote installation
• Compound barrier type flameproof seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Integral protected deluge seal
• -60?C to +85?C
• Class I Zone 1, 21 and Zone 2, 22 Class I Division 1 & 2 ABCD
• Globally marked, IECEx, ATEX, UL & cCSAus
• EMC tested

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables.

For under / oversized armour wires click here

Design SpecificationBS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications *Impact = Level 8, Retention = Class D
Enclosure ProtectionIK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications *Category B (Category A when used with braid, tape or pliable wire armour cables)
ATEX CertificateSIRA13ATEX1072X, SIRA13ATEX4078X
Code of Protection II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da
II 3G Ex nR IIC Gc, IM2 Ex d I Mb, Ex e I Mb
Compliance StandardsEN 60079-0,1,7,15,31
IECEx CertificateIECEx SIR 13.0027X, IECEx SIM 14.0008X
Code of ProtectionEx d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
Compliance StandardsIEC 60079-0,1,7,15,31
cCSAus Certificate (20s16 - 100)2288626
CSAus Code of Protection***Class I, Div. 1, 2 Groups A, B, C and D; Class II, Div. 1, 2 Groups E, F and G; Class III, Div. 1, 2; Type 4X: Oil Resistant II:
Class I, Zone 1 AEx d IIC Gb, AEx e IIC Gb, Class I, Zone 2 AEx nR IIC Gc, Class I, Zone 20 AEx ta IIIC Da
cCSA Code of Protection***Class I, Div. 1, 2 Groups A, B, C and D; Class II, Div. 1, 2 Groups E, F and G; Class III, Div. 1, 2; Type
4X: Oil Resistant II:
Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da
Compliance StandardsCAN/CSA-C22.2 No 0,18,25,30,94,174, CAN/CSA-E60079-0,1,7,15,31 CAN/CSA-E61241-1-1 Part
1-1, ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079
UL Certificate (20s16 - 100)E201187, E161256C
Code of ProtectionClass I Div 1,2, Groups A,B,C,D, Class II Div 1,2, Groups E,F,G
Compliance StandardsUL 2225, CSA C22.2 No 174, UL 514B, CSA C22.2 No 18, CSA C22.2 No 30
UkrSEPROUA.TR.047.C.0644-15
EAC CertificateC-GB.AA87.B.00487
KCC Certificate14-GA4BO-0252X
CCOE / PESO (India) CertificateP333688
NEPSI CertificateGYJ13.1140X, GYJ13.1282X
INMETRO ApprovalTÜV 12.2073X
RETIE Certificate03866
Marine ApprovalsLRS: 01/00172, DNV: TAE00000Y, ABS: 14-LD234401A-4-PDA, BV: 43180/A1BV
Ingress Protection Rating **IP66, IP67 & IP68
Deluge Protection ComplianceDTS01 : 91
Cable Gland MaterialBrass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal MaterialCMP SOLO LSF Halogen Free Thermoset Elastomer / Epoxy Barrier Compound
Cable TypeSingle Wire Armour (SWA), Aluminium Wire Armour (AWA), Wire Braid Armour (e.g. SWB),
Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Pliable Wire Armour (PWA), Steel Tape
Armour (STA), Strip Armour (e.g. ASA)***
Armour ClampingDetachable Compound Tube / Cone & AnyWay Universal Clamping Ring
Sealing TechniqueUnique CMP ‘LRS’ Outer Seal (Load Retention Seal)
Sealing Area(s)Inner Compound Barrier & Outer Sheath
Optional AccessoriesLocknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation ToolsSpanners, Armour Former Tool

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to Maintaining a Seal for further information.
*** Where the cable is permitted by code (NEC and/or CEC)
**** IP68 tested to a minimum depth of 30 metres for 12 hours, alternate depths / durations can be provided upon request

Certificates

Click here to view Certificates

Product Selection Table

Click here to view Technical Illustration

Technical Illustration

Click here to view how to order

Cable Gland SizeAvailable Entry Threads ?C? (Alternate Metric Thread Lengths Available)Number of CoresDiameter Over Conductors
?A?
Cable Bedding Diameter ?G?Overall
Cable
Diameter
?B?
Armour RangeAcross
Flats
?D?
Across
Corners
?D?
Protrusion
Length ?F?
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
StandardOptionGrooved
Cone (X)
Stepped Cone (W)
MetricThread Length (Metric) ?E?NPTThread Length
(NPT) ?E?
NPTMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M200.59½?0.78¾"110.460.460.240.520.010.040.030.051.201.322.4420S16PX2K1RAPVC068.47
20SM200.59½?0.78¾"110.460.460.370.630.010.040.030.051.201.322.4420SPX2K1RAPVC068.11
20M200.59½?0.78¾"110.500.510.490.820.020.040.030.051.201.322.4820PX2K1RAPVC068.47
25SM250.59¾?0.801"210.690.700.550.870.020.050.050.061.481.632.7425SPX2K1RAPVC0913.05
25M250.59¾?0.801"210.690.700.721.030.020.050.050.061.481.632.7425PX2K1RAPVC0913.05
32M320.591?0.981 ¼"380.930.940.931.330.020.050.060.081.811.992.9532PX2K1RAPVC1120.11
40M400.591 ¼?1.011 ½"591.181.191.101.590.020.060.060.082.172.382.9540PX2K1RAPVC1528.22
50SM500.591 ½?1.032"891.441.451.391.840.020.060.080.102.362.603.0350SPX2K1RAPVC1831.75
50M500.592?1.062 ½"891.611.631.592.090.020.060.080.102.763.033.0350PX2K1RAPVC2141.98
63SM630.592?1.062 ½"1151.891.911.802.340.020.060.080.102.953.253.1463SPX2K1RAPVC2349.03
63M630.592 ½?1.573"1152.112.132.152.590.020.060.080.103.153.463.1663PX2K1RAPVC2549.74
75SM750.592 ½?1.573"1402.362.372.322.830.020.060.080.103.543.903.4275SPX2K1RAPVC2873.72
75M750.593?1.633 ½"1402.532.532.633.090.020.060.100.123.944.333.4875PX2K1RAPVC3089.60
90M900.943 ½?1.694"2002.962.983.003.560.030.060.120.164.534.984.0290PX2K1RAPVC32130.87
100M1000.943 ½?1.694"2003.373.383.393.990.030.060.120.165.005.504.49100PX2K1RALSF33152.03
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads ?C? (Alternate Metric Thread Lengths Available)Number of CoresDiameter Over Conductors
?A?
Cable Bedding Diameter ?G?Overall
Cable
Diameter
?B?
Armour RangeAcross
Flats
?D?
Across
Corners
?D?
Protrusion
Length ?F?
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOptionGrooved
Cone (X)
Stepped Cone (W)
MetricThread Length (Metric) ?E?NPTThread Length
(NPT) ?E?
NPTMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M2015.0½?19.9¾"1111.711.76.113.10.31.00.81.2530.533.662.020S16PX2K1RAPVC060.24
20SM2015.0½?19.9¾"1111.711.79.515.90.31.00.81.2530.533.662.020SPX2K1RAPVC060.23
20M2015.0½?19.9¾"1112.612.912.520.90.41.00.81.2530.533.663.020PX2K1RAPVC060.24
25SM2515.0¾?20.21"2117.517.914.022.00.41.21.251.637.541.369.525SPX2K1RAPVC090.37
25M2515.0¾?20.21"2117.517.918.226.20.41.21.251.637.541.369.525PX2K1RAPVC090.37
32M3215.01?25.01 ¼"3823.623.923.733.90.41.21.62.046.050.675.032PX2K1RAPVC110.57
40M4015.01 ¼?25.61 ½"5930.030.327.940.40.41.61.62.055.060.575.040PX2K1RAPVC150.80
50SM5015.01 ½?26.12"8936.636.935.246.70.41.62.02.560.066.077.050SPX2K1RAPVC180.90
50M5015.02?26.92 ½"8941.041.340.453.00.61.62.02.570.077.077.050PX2K1RAPVC211.19
63SM6315.02?26.92 ½"11547.948.445.659.40.61.62.02.575.082.579.763SPX2K1RAPVC231.39
63M6315.02 ½?39.93"11553.754.054.665.80.61.62.02.580.088.080.363PX2K1RAPVC251.41
75SM7515.02 ½?39.93"14059.960.259.072.00.61.62.02.590.099.086.875SPX2K1RAPVC282.09
75M7515.03?41.53 ½"14064.264.266.778.40.61.62.53.0100.0110.088.375PX2K1RAPVC302.54
90M9024.03 ½?42.84"20075.375.676.290.30.81.63.154.0115.0126.5102.190PX2K1RAPVC323.71
100M10024.03 ½?42.84"20085.685.986.1101.40.81.63.154.0127.0139.7114.0100PX2K1RALSF334.31
Dimensions displayed in millimeters unless otherwise stated