FORTRA E1FW | Explosive Atmosphere Cable Gland For All Types of Steel and Aluminium Wire Armoured Cables
- Ex nR
- Ex ta
- Ex e
- Ex d
FORTRA E1FW | Explosive Atmosphere Cable Gland For All Types of Steel and Aluminium Wire Armoured Cables
We'd like to keep in touch
We have some exciting things in the pipeline - if you'd like to be the first to know please enter your email address below.
- Flameproof inner diaphragm seal – safe, reliable & robust; no installation or inspection ambiguity
- Excellent cold flow performance with third party verified test report on cable types used globally
- Dedicated captive cone for wire armour, with ‘AnyWay’ clamping ring
- Metal-to-metal armour clamping; no installation or inspection ambiguity
- Outer seal with wider cable acceptance, meaning fewer stocking sizes
- IP66 as standard with option to fit fully enclosed/protected deluge seal for IP67 68 69 & 69K & third party compliance to DTS 01:91 & NEMA 4X & 6P
- Compact design; ideal for applications with limited installation space
- Fewer installation steps for faster process
- Fewer tools required for installation and maintenance
| Design Specification | BS 6121-1, IEC 62444, EN 62444 |
| Mechanical Classifications* | 16-20S Impact = Category 6, 20-130 Impact = Category 8 Wire Armour Anchorage = Type D |
| Enclosure Protection | 16-20S IK08 to IEC 62262 (7 joules) 20-130 IK10 to IEC 62262 (20 joules)) |
| Electrical Classifications * | Category B |
| Ingress Protection Rating** | IP66 as standard (Order E1FWD for IP67, IP68***, IP69 and IP69K option) |
| Type Rating** | Order E1FWD for NEMA 4X & 6P |
| Deluge Protection Compliance | Order E1FWD for compliance with DTS 01:91 |
| Temperature for permanent application | -60 to +105 °C |
| Armour Clamping | Dedicated Captive Armour Cone and 'AnyWay' Clamping Ring |
| Seal Material | LSF Halogen Free Silicone |
| Sealing Technique | CMP Inner Flameproof Diaphragm Seal and Outer Environmental/Load Retention Seal |
| Sealing Area(s) | Cable Inner Bedding and Cable Outer Sheath |
| Type Material Options | Brass†, Electroless Nickel Plated Brass, Aluminium, Stainless Steel |
| Cable Type (s) | Single Wire Armour (SWA), Aluminium Wire Armour (AWA) |
| ATEX Certificate | CML 24ATEX1333X, CML 24ATEX4334X |
| UKEX Certificate | CML 24UKEX1335X, CML 24UKEX4336X |
| Code of Protection | Ex I M2 Ex db I Mb, Ex eb I Mb; Ex II 2G 3G 1D Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da, Ex nR IIC Gc |
| Compliance Standards | EN 60079- 0, -1, -7, -15, -31 |
| IECEx Certificate | IECEx CML 24.0137X |
| Code of Protection | Ex db I Mb, Ex eb I Mb, Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da, Ex nR IIC Gc |
| Compliance Standards | IEC 60079- 0, -1, -7, -15, -31 |
| EAC Certificate | EAЭC KZ 7100841.01.01.07859 |
| Code of Protection | Ex 1Ex db IIC Gb X, Ex 1Ex eb IIC Gb X, Ex 2Ex nR IIC Gc X, Ex Ex ta IIIC Da X |
| UkrSEPRO | CЦ 25.1094X |
| Marine Approvals | Lloyds: LR22320255TA, ABS: 25-0285992-PDA, DNV: TAE000000Y, BV: 43180 |
| INMETRO Certificate | INMETRO TÜV 25.0801X |
| Industrial Certificate | CML 24CA17921 |
| Taiwan Certificate | Taiwan: ML141200751312 |
| PESO | P640726/2, P640727/6 |
| CCC Certificate | CCC 2026322313007163 |
* Mechanical and Electrical Classifications applied as per IEC 62444 and EN 62444
** When CMP installation accessories are used. Refer to www.cmp-products.com for
further information
*** IP68 tested to a depth of 30 metres for 7 days, alternative depths / durations can
be provided on request
† Not available with NEMA type 4X and 6P
Certificates
Product Selection Table
Click here to view how to order
| Combined Ordering Reference | Entry Thread Size ‘TS’ | Entry Thread Pitch | Minimum Thread Length ‘TL’ | Inner Cable Bedding Diameter ‘IB’ | Overall Cable Diameter ‘OS’ | Armour Thickness | Max Across Flats | Max Across Corners ‘AC’ | Max Protrusion Length ‘PL’ | Shroud Size | Assembly Weight (oz) |
|||||
| Size | Type | Ordering Suffix | Min | Max | Min | Max | Mix | Max | ||||||||
| 20S16‡ | E1W | 502 | M20 | 0.06 | 0.39 | 0.12 | 0.28 | 0.24 | 0.52 | 0.03 | 0.05 | 0.94 | 1.04 | 2.2 | 4 | 0.11 |
| 20S‡ | E1W | 502 | M20 | 0.06 | 0.39 | 0.24 | 0.46 | 0.37 | 0.63 | 0.03 | 0.05 | 0.94 | 1.04 | 2.2 | 4 | 0.1 |
| 20 | E1W | 502 | M20 | 0.06 | 0.39 | 0.31 | 0.55 | 0.49 | 0.82 | 0.03 | 0.05 | 1.18 | 1.3 | 2.36 | 6 | 0.17 |
| 25 | E1W | 503 | M25 | 0.06 | 0.39 | 0.43 | 0.77 | 0.63 | 1.03 | 0.05 | 0.06 | 1.48 | 1.63 | 2.89 | 9 | 0.3 |
| 32 | E1W | 504 | M32 | 0.06 | 0.39 | 0.67 | 1.04 | 0.85 | 1.33 | 0.06 | 0.08 | 1.81 | 1.99 | 3.09 | 11 | 0.44 |
| 40 | E1W | 505 | M40 | 0.06 | 0.59 | 0.87 | 1.26 | 1.1 | 1.59 | 0.06 | 0.08 | 2.17 | 2.38 | 3.29 | 15 | 0.63 |
| 50 | E1W | 506 | M50 | 0.06 | 0.59 | 1.16 | 1.73 | 1.5 | 2.09 | 0.08 | 0.1 | 2.76 | 3.03 | 3.74 | 21 | 1.05 |
| 63 | E1W | 507 | M63 | 0.06 | 0.59 | 1.63 | 2.17 | 2.05 | 2.6 | 0.08 | 0.1 | 3.15 | 3.46 | 4.17 | 25 | 1.28 |
| 75 | E1W | 508 | M75 | 0.06 | 0.59 | 2.11 | 2.68 | 2.54 | 3.09 | 0.1 | 0.12 | 3.94 | 4.33 | 4.17 | 30 | 2.24 |
| 90 | E1WD | 509 | M90 | 0.08 | 0.94 | 2.6 | 3.09 | 2.95 | 3.56 | 0.12 | 0.16 | 4.49 | 4.94 | 5.35 | 32 | 4.3 |
| 100 | E1WD | 5010 | M100 | 0.08 | 0.94 | 2.99 | 3.56 | 3.39 | 4 | 0.12 | 0.16 | 4.84 | 5.33 | 5.55 | 33 | 4.42 |
| 115 | E1WD | 5011 | M115 | 0.08 | 0.94 | 3.39 | 3.86 | 3.98 | 4.35 | 0.12 | 0.16 | 5.24 | 5.76 | 6.12 | 34 | 6.13 |
| 130 | E1WD | 5012 | M130 | 0.08 | 0.94 | 3.84 | 4.53 | 4.33 | 4.86 | 0.12 | 0.16 | 6.02 | 6.63 | 6.52 | 35 | 8.11 |
| Dimensions listed are for cable glands with metric equipment entry threads only. Alternative entry thread types e.g. NPT are available; dimensions may vary. | ||||||||||||||||
| Part numbers listed are for nickel plated brass cable glands only. Alternative materials are available. ‡ Also available in M16 on request | ||||||||||||||||
| For material options, please change the ‘material suffix’, which is the first digit in the ‘ordering suffix’. Brass = 0, Stainless Steel = 4 and Nickel Plated Brass = 5. Examples: 20E1W002 = Brass M20, 40E1W405 = Stainless Steel M40 |
||||||||||||||||
| For NPT thread options, please change the second digit in the ‘ordering suffix’ to 3 (denotes NPT) and change the final digit to denote the thread size i.e. ½” = 31, ¾” = 32, 1” = 33, 1-1/4” = 34, 1-1/2” = 35, 2” = 36, 2-1/2” = 37, 3” = 38, 3-1-2” = 39, 4” = 310, 5” = 312. Examples: 32E1W533 = Nickel Plated Brass 1” NPT, 50E1W436 = Stainless Steel 2” NPT |
||||||||||||||||
| Combined Ordering Reference | Entry Thread Size ‘TS’ | Entry Thread Pitch | Minimum Thread Length ‘TL’ | Inner Cable Bedding Diameter ‘IB’ | Overall Cable Diameter ‘OS’ | Armour Thickness | Max Across Flats | Max Across Corners ‘AC’ | Max Protrusion Length ‘PL’ | Shroud Size | Assembly Weight (KG) |
|||||
| Size | Type | Ordering Suffix | Min | Max | Min | Max | Mix | Max | ||||||||
| 20S16‡ | E1FW | 502 | M20 | 1.5 | 15 | 3.1 | 7 | 6.1 | 13.2 | 0.8 | 1.25 | 24 | 26.4 | 56 | 4 | 0.11 |
| 20S‡ | E1FW | 502 | M20 | 1.5 | 15 | 6 | 11.6 | 9.5 | 15.9 | 0.8 | 1.25 | 24 | 26.4 | 56 | 4 | 0.11 |
| 20 | E1FW | 502 | M20 | 1.5 | 15 | 8 | 14 | 12.5 | 20.9 | 0.8 | 1.25 | 30 | 33 | 60 | 6 | 0.17 |
| 25 | E1FW | 503 | M25 | 1.5 | 15 | 11 | 19.5 | 16 | 26.2 | 1.25 | 1.6 | 37.5 | 41.3 | 73.5 | 9 | 0.3 |
| 32 | E1FW | 504 | M32 | 1.5 | 15 | 17 | 26.5 | 21.5 | 33.9 | 1.6 | 2 | 46 | 50.6 | 78.5 | 11 | 0.44 |
| 40 | E1FW | 505 | M40 | 1.5 | 15 | 22 | 32 | 28 | 40.4 | 1.6 | 2 | 55 | 60.5 | 83.5 | 15 | 0.63 |
| 50 | E1FW | 506 | M50 | 1.5 | 15 | 29.5 | 44 | 38 | 53.2 | 2 | 2.5 | 70 | 77 | 95 | 21 | 1.05 |
| 63 | E1FW | 507 | M63 | 1.5 | 15 | 41.5 | 55 | 52 | 66 | 2 | 2.5 | 80 | 88 | 106 | 25 | 1.28 |
| 75 | E1FW | 508 | M75 | 1.5 | 15 | 53.5 | 68 | 64.5 | 78.5 | 2.5 | 3.15 | 100 | 110 | 106 | 30 | 2.24 |
| 90 | E1FWD | 509 | M90 | 2 | 24 | 66 | 78.5 | 75 | 90.5 | 3.15 | 4 | 114 | 125.4 | 136 | 32 | 4.3 |
| 100 | E1FWD | 5010 | M100 | 2 | 24 | 76 | 90.5 | 86 | 101.5 | 3.15 | 4 | 123 | 135.3 | 141 | 33 | 4.42 |
| 115 | E1FWD | 5011 | M115 | 2 | 24 | 86 | 98 | 101 | 110.5 | 3.15 | 4 | 133 | 146.3 | 155.5 | 34 | 6.13 |
| 130 | E1FWD | 5012 | M130 | 2 | 24 | 97.5 | 115 | 110 | 123.5 | 3.15 | 4 | 153 | 168.3 | 165.7 | 35 | 8.11 |
| Dimensions listed are for cable glands with metric equipment entry threads only. Alternative entry thread types e.g. NPT are available; dimensions may vary. | ||||||||||||||||
| Part numbers listed are for nickel plated brass cable glands only. Alternative materials are available. ‡ Also available in M16 on request | ||||||||||||||||
| For material options, please change the ‘material suffix’, which is the first digit in the ‘ordering suffix’. Brass = 0, Stainless Steel = 4 and Nickel Plated Brass = 5. Examples: 20E1FW002 = Brass M20, 40E1FW405 = Stainless Steel M40 |
||||||||||||||||
| For NPT thread options, please change the second digit in the ‘ordering suffix’ to 3 (denotes NPT) and change the final digit to denote the thread size i.e. ½” = 31, ¾” = 32, 1” = 33, 1-1/4” = 34, 1-1/2” = 35, 2” = 36, 2-1/2” = 37, 3” = 38, 3-1-2” = 39, 4” = 310, 5” = 312. Examples: 32E1FW533 = Nickel Plated Brass 1” NPT, 50E1FW436 = Stainless Steel 2” NPT |
||||||||||||||||
DIN 40050 Definitions
The following page provides an explanation of ingress protection codes according to DIN 40050-9 (liquids) and IEC 60529 (dusts).
Read moreElectrical Safety in the Work Place
Local codes of practice or regulations may be in force to ensure that safety is maintained to eliminate the possibility of accidents arising from the danger of electricity. These dangers would include electric shock, burns, fire, explosion and arcing. In the United Kingdom the ESQCR 2002, and amendments 2006 (S.I. No. 1521) and 2009 (S.I. No. 639), introduced under Statutory Instrument No. 2665, and the Electricity at Work Regulations 1989 (EAW Regulations), which came into force on 1 April 1990, comprehensively deal with this subject.
Read moreEMC Performance
Tests were carried out in an anechoic chamber using various CMP cable glands with a section of cable connected to it which would act as an aerial. A known electrical radiation source was used to introduce interference into the chamber, and the level of radiation in the cable shield was measured.
Read moreVisit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.
Log in now