TMC2X | Class I, Div 1 & 2 | AEx d, AEx e, AEx t | Hazardous (Classified) Location Barrier Cable Gland For MC, MC-HL, Interlocked & Teck Armored Cables

Globally Approved, Hazardous (Classified) Location Barrier Cable Gland

  • RapidEx liquid pour sealing system reduces installation time
  • Simplified two part design
  • Compact slim profile
  • Independent sealing and armor clamping
  • Simple, sequential installation process
  • Low impedance copper plated stainless steel 360° grounding spring
  • Disconnectable, union design feature
  • -60°C to +85°C (-76˚F to +185˚F)
  • Globally marked, cCSAus, cULus, IECEx and ATEX

Note: Supplied in pack with RapidEx resin

Patents Granted: ES2287986, NO 2287986, TR 2287986, AU 2010284848, AU 2014274614, GB 2485114, SG 178839, US 8872027, US 9484133, US 9774178, MY 153843, US 10193321, US 1034078

 

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classification* Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
ATEX Certificate CML 18ATEX1336X
Code of Protection II 2G 1D, Ex db IIC, Ex eb IIC Gb, Ex ta IIIC Da
Compliance Standards EN 60079-0,1,7,31
IECEx Certificate IECEx CML 18.0193X
Code of Protection Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
Compliance Standards IEC 60079-0,1,7,31
cCSAus Certificate 2194053
CSAus Code of Protection Class I, Div 1 and 2, Groups A,B,C, and D; Class II, Div 1 and 2, Groups E, F, and G; Class III, Div 1 and 2; Encl. Type 4X; Ex d IIC; Ex e II; Class I, Zone 1, AEx d IIC; AEx e II; AEx ta IIIC
cCSA Code of Protection Class I, Div 1 and 2, Groups A, B, C, and D; Class II, Div 1 and 2, Groups E, F, and G; Class III,
Div 1 and 2; Encl. Type 4X; Ex d IIC; Ex e II; Class I, Zone 1, AEx d IIC; AEx e II; AEx ta IIIC
Compliance Standards CAN/CSA-C22.2 No 0-M91,18-04, 25-1966,30-M1986,174-M1984,94-M91,
CAN/CSA-60079-0,1,7, CAN/CSA-E61241-1-1, ANSI/UL 514B, ANSI/UL 50, ANSI/UL 2225
cULus Certificate (075-162) E161256
Code of Protection Class I, Div 1 and 2, Groups A, B, C, and D; Class II, Div 1 and 2, Groups E, F, and G; Class III, Div 1 and 2
Compliance Standards UL2225, UL514B, CSA C22.2 No. 174-18, 18.3-12
ECAS Certificate 20-02-06423
UkrSEPRO CЦ 19.0371X
EAC Certificate TC RU C-GB.AA87.B.00487
Code of Protection 1Ex d IIC Gb X, 1Ex e IIC Gb X, Ex ta IIIC Da X, IP66
RETIE Approval 03866
CCOE / PESO (India) Certificate P444949
Marine Approvals LRS: 01/00172, DNV: TAE000000Y, 20-2022051-PDA, BV: 43180 A1 BV
Ingress Protection Rating** IP66
NEMA Rating** NEMA 4X
Cable Type Corrugated & Interlocked Metal Clad Armor (MC) or TECK90, Continuously Welded Metal Clad Armor (MCHL), ACIC-HL, ACWU90-HL, RC90-HL, RA90-HL
Armor Clamping Low Impedance Copper Plated Stainless Steel 360° Grounding Spring
Jacket Sealing Technique CMP Load Retention Seal
Sealing Area(s) RapidEx Liquid Resin, Cable Outer Jacket
Cable Gland Material Copper Free (<0.4%) Aluminium, Stainless Steel, Electroless Nickel Plated Brass

Note : * Mechanical and Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to Maintaining a Seal for further information.

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Order Reference (NPT with RapidEx Resin)Entry Thread 'C'Minimum Thread Length 'E'Cable Armor Diameter 'A'Cable Jacket Diameter 'B'Max Over Conductors 'G'Across Flats 'D'Across Corners 'D'Nominal Assembly Length 'F'ShroudApprox Weight Aluminum (oz)
AluminumNickel Plated BrassStainless SteelNPTNPT OptionArmor Stop InArmor Stop OutMinMaxMaxMax
MinMaxMinMax
TMC2X-050A075XTMC2X-050NB075XTMC2X-050SS075X½"-0.780.420.550.550.630.5000.7500.511.201.322.44PVC062.29
TMC2X-075A075XTMC2X-075NB075XTMC2X-075SS075X-¾"0.800.420.550.550.630.51PVC09
TMC2X-050A099XTMC2X-050NB099XTMC2X-050SS099X½"-0.780.600.650.650.890.6900.9900.511.481.632.96PVC093.00
TMC2X-075A099XTMC2X-075NB099XTMC2X-075SS099X-¾"0.800.600.780.780.890.71
TMC2X-075A118XTMC2X-075NB118XTMC2X-075SS118X¾"-0.800.790.860.861.100.8701.1800.711.811.993.15PVC115.11
TMC2X-100A118XTMC2X-100NB118XTMC2X-100SS118X-1"0.980.790.980.981.100.94
TMC2X-100A137XTMC2X-100NB137XTMC2X-100SS137X1"-0.980.941.081.081.281.0201.3700.942.052.263.55PVC156.70
TMC2X-125A137XTMC2X-125NB137XTMC2X-125SS137X-1 ¼"1.010.941.181.181.281.20
TMC2X-125A162XTMC2X-125NB162XTMC2X-125SS162X1 ¼"-1.011.221.351.351.501.3001.6201.202.362.603.59PVC188.82
TMC2X-150A162XTMC2X-150NB162XTMC2X-150SS162X-1 ½"1.031.221.421.421.501.46
TMC2X-125A190XTMC2X-125NB190XTMC2X-125SS190X1 ¼"-1.01--1.511.721.5701.9001.202.562.823.59PVC379.45
TMC2X-150A190XTMC2X-150NB190XTMC2X-150SS190X-1 ½"1.03--1.511.721.46
TMC2X-150A200XTMC2X-150NB200XTMC2X-150SS200X1 ½"-1.031.571.701.701.881.6502.0001.462.753.033.76PVC2111.06
TMC2X-200A200XTMC2X-200NB200XTMC2X-200SS200X-2"1.061.571.701.701.881.63
TMC2X-150A233XTMC2X-150NB233XTMC2X-150SS233X-1 ½"1.03--1.812.211.9102.3301.462.953.253.97PVC2312.77
TMC2X-200A233XTMC2X-200NB233XTMC2X-200SS233X2"-1.06--1.812.211.90
TMC2X-250A233XTMC2X-250NB233XTMC2X-250SS233X-2 ½"1.57--1.812.212.133.543.89PVC28
TMC2X-200A272XTMC2X-200NB272XTMC2X-200SS272X-2"1.062.142.462.172.612.2702.7201.903.543.894.10PVC2824.69
TMC2X-250A272XTMC2X-250NB272XTMC2X-250SS272X2 ½"-1.572.142.462.462.612.13
TMC2X-300A272XTMC2X-300NB272XTMC2X-300SS272X-3"1.632.142.462.462.612.554.334.76PVC31
TMC2X-300A325XTMC2X-300NB325XTMC2X-300SS325X3"-1.632.492.782.782.972.6203.2502.984.334.764.67PVC3142.68
TMC2X-350A325XTMC2X-350NB325XTMC2X-350SS325X-3 ½"1.692.492.782.782.972.98
TMC2X-350A376XTMC2X-350NB376XTMC2X-350SS376X3 ½"-1.692.953.453.453.543.1603.7603.384.845.324.95LSF3353.44
TMC2X-400A376XTMC2X-400NB376XTMC2X-400SS376X-4"1.732.953.453.453.543.38
TMC2X-400A425XTMC2X-400NB425XTMC2X-400SS425X4"-1.73--3.563.943.7004.2503.385.235.755.16LSF3459.19
Order code example: TMC2X-050A075 - “TMC2X” (Gland Type) - “050” (½” NPT Thread) - ‘A’ (Material Aluminum) - “075” (Max Cable Diameter 0.75”)
TMC2X*075-162 cULus Listed
Dimensions are displayed in inches unless otherwise stated

Technical Illustration