Product Search
EN-US EN-GB RU CN

Olympus (SHVSS) Single High Voltage Cable Cleat

CMP OLYMPUS single cable cleat is a composite cable cleat which has been designed, constructed and tested in accordance with the International Standard ‘cable cleats for electrical installations’ IEC 61914:2015 to ensure the securing and retention of cables, without sustaining damage.

The stainless steel section of this cable cleat can be optionally coated with an extremely high performance UL94 V0 flame retardant. This low toxicity polymer alloy coating is halogen free polymer and low smoke & fume, whilst being resistant to: impact, abrasion, salt spray, chemical attack, weathering & UV, making it perfectly suited for use in rail applications.

OLYMPUS cable cleats are designed to be installed as a system for use with High Voltage cable installations and can be manufactured in a standard set of cable diameter range or to suit specific project parameters.

Fabricated in non-magnetic 316L stainless steel, giving it high creep strength whilst providing excellent corrosion resistance in the harshest environments.

Flame retardant low smoke and fume, zero halogen(FR LSF/LSOH) polymeric fixed liners are fitted as standard, helping to:

  • Restrain the cables within vertical applications.
  • Provide a layer of protection to both the cable sheath and
    the cable cleat, during normal operation where thermal
    elongation of cable occurs.
  • Protect the cable from chafing on any mounting surface
    due to differential movements, such as those found in
    marine and offshore applications.
  • Assist in the extra protection of cables in the event of
    short circuit fault conditions

Features

  • Third party tested in accordance with IEC 61914:2015
  • Available in 316L stainless steel
  • Sunlight (UV) resistant
  • Operating temperature -50°C to +60°C
  • Excellent axial and lateral load retention
SHORT CIRCUIT TESTING TO IEC 61914 - CLAUSE 9.5
FLAT/PARALLEL FORMATION
TWO SHORT CIRCUIT 2.4mTWO SHORT CIRCUIT 1.5m
290mm conductor centres290mm conductor centres
1 sec1 sec
176kA Peak160kA Peak
63 kA r.m.s64 kA r.m.s
Type 6.1.3 Composite
Design Specification IEC 61914
Temperature for permanent application -60°C to + 60°C
IEC 61914 clause / part 6.2
Needle Flame Test Pass - 120 seconds
IEC 61914 clause
10.0, 10.1, IEC 60695-11-5
Impact Resistance Pass - Very Heavy
IEC 61914 clause 6.3, 6.3.5, 9.2
Material 316L Stainless Steel
Material Thickness 2mm
Liner Material FR LSF / LSOH Polymer
Cable Formation Parallel
Lateral Load Test 33 kN
Axial Load Test 4.5 kN

Product Selection Table

OLYMPUS PART NO.CABLE Ø RANGE TAKE (inch)Dimensions (inch)Weight (oz)
WHDP*fixing hole ø
SHVSS0901003.54 - 3.946.75.337.093.942 X M1677.6
SHVSS1001103.94 - 4.337.255.927.093.942 X M1684.66
SHVSS1101204.33 - 4.727.596.127.093.942 X M1689.95
SHVSS1201304.72 - 5.128.036.517.093.942 X M1693.48
SHVSS1301405.12 - 5.518.486.877.095.512 X M16100.53
SHVSS1401505.51 - 5.918.857.267.095.512 X M16104.06
SHVSS1501605.91 - 6.309.227.667.095.512 X M16107.59
SHVSS1601706.30 - 6.699.588.067.095.512 X M16111.11
SHVSS1701806.69 - 7.09108.457.097.092 X M16118.17
SHVSS1801907.09 - 7.4810.448.847.097.092 X M16123.46
SHVSS1902007.48 - 7.8710.819.247.097.092 X M16126.99

Technical Illustration