Product Search
EN-US EN-GB RU CN

Titan (SCSS) High Voltage Trefoil Saddle Cable Cleat

The TITAN cable support cleat has been designed, constructed and tested in accordance with the international standard IEC 61914:2015 cable cleats for electrical installations; to ensure the securing and retention of cables, without sustaining damage to the cable(s).

Designed to support cables in high voltage applications, the TITAN allows cable sag between fixed anchor points,
where desirable. Sagging cable between fixed anchor points is a method of installation where the cable is allowed to hang between the cleats. This area of excess cable will accommodate thermal expansion and contraction of the cable in service, without putting undue stress on the anchor points.

The TITAN adds additional support to the cable at the anchor points, ensuring there is no excessive pressure or point loading to the cable in these critical areas. The system is designed so that the support arm and cleat area can swivel and rotate, allowing flexibility to the installer.

The TITAN comes in three lengths; 400mm, 600mm and 800mm. This will accommodate larger cable cleat fixing centers, whilst reducing the pressure applied t the cable from its own weight.

The product can be fabricated to suit any installation parameters. Please contact CMP to discuss your specific project requirements.

Features

  • Third party tested in accordance with IEC 61914:2015
  • Highly corrosion resistant stainless steel
  • Sunlight (UV) resistant
  • Operating temperature -60°C to +60°C
  • Allows cable sag between fixed anchor points
  • Increased support reducing pressure on cable
  • Strong heavy duty construction
SHORT CIRCUIT TESTING TO IEC 61914 - CLAUSE 9.5
TREFOIL FORMATION
One Short Circuit 8.4m,
with intermediate restraints
Two Short Circuit 8.4m,
with intermediate restraints
142mm conductor centres142mm conductor centres
1 sec1 sec
183kA Peak153 kA Peak
72 kA r.m.s60 kA r.m.s
Type 6.1.3 Composite
Design Specification IEC 61914:2015
Temperature for permanent application -60°C to + 60°C
IEC 61914 clause / part 6.2
Needle Flame Test Pass - 120 seconds
IEC 61914 clause
10.0, 10.1, IEC 60695-11-5
Impact Resistance Pass - Very Heavy
IEC 61914 clause 6.3, 6.3.5, 9.2
Material Stainless steel
Liner Material FR LSF / LSOH Polymer
Cable Formation Trefoil

Product Selection Table

TITAN Part No.Cable ø range take (inch)Length (inch)Dimensions (icnh)BASE FIXINGWEIGHT (oz)
HWLL2W2P
SCSS-100110-4003.94 - 4.3315.7511.3311.7515.753.546.694.722 x M16266.00
SCSS-100110-6003.94 - 4.3323.6211.3311.7523.623.546.694.722 x M16333.27
SCSS-100110-8003.94 - 4.3331.5011.3311.7531.503.546.694.722 x M16399.90
SCSS-110120-4004.33 - 4.7215.7512.0612.5415.753.547.094.722 x M16301.95
SCSS-110120-6004.33 - 4.7223.6212.0612.5423.623.547.094.722 x M16377.18
SCSS-110120-8004.33 - 4.7231.5012.0612.5431.503.547.094.722 x M16448.12
SCSS-120130-4004.72 - 5.1215.7512.8013.3315.753.547.484.722 x M16296.44
SCSS-120130-6004.72 - 5.1223.6212.8013.3323.623.547.484.722 x M16372.49
SCSS-120130-8004.72 - 5.1231.5012.8013.3331.503.540.754.722 x M16447.70
SCSS-130140-4005.12 5.5115.7513.5314.1315.753.547.874.722 x M16311.72
SCSS-130140-6005.12 5.5123.6213.5314.1323.623.547.874.722 x M16392.32
SCSS-130140-8005.12 5.5131.5013.5314.1331.503.547.874.722 x M16462.97
SCSS-140150-4005.51 - 5.9115.7514.2714.9215.753.548.275.512 x M16326.92
SCSS-140150-6005.51 - 5.9123.6214.2714.9223.623.548.275.512 x M16426.85
SCSS-140150-8005.51 - 5.9131.5014.2714.9231.503.548.275.512 x M16491.51
SCSS-150160-4005.91 - 6.3015.7515.0015.7115.753.548.665.512 x M16342.23
SCSS-150160-6005.91 - 6.3023.6215.0015.7123.623.548.665.512 x M16431.68
SCSS-150160-8005.91 - 6.3031.5015.0015.7131.503.548.665.512 x M16519.90
SCSS-160170-4006.30 - 6.6915.7515.7416.5115.753.549.065.512 x M16357.47
SCSS-160170-6006.30 - 6.6923.6215.7416.5123.623.549.065.512 x M16451.40
SCSS-160170-8006.30 - 6.6931.5015.7416.5131.503.549.065.512 x M16539.02
SCSS-170180-4006.69 - 7.0915.7516.4717.3015.753.549.456.302 x M16372.78
SCSS-170180-6006.69 - 7.0923.6216.4717.3023.623.549.456.302 x M16471.05
SCSS-170180-8006.69 - 7.0931.5016.4717.3031.503.549.456.302 x M16563.01
SCSS-180190-4007.09 - 7.4815.7517.2018.0915.753.549.846.302 x M16388.08
SCSS-180190-6007.09 - 7.4823.6217.2018.0923.623.549.846.302 x M16490.91
SCSS-180190-8007.09 - 7.4831.5017.2018.0931.503.549.846.302 x M16586.96
SCSS-190200-4007.48 - 7.8715.7517.9418.8915.753.5410.246.302 x M16403.68
SCSS-190200-6007.48 - 7.8723.6217.9418.8923.623.5410.246.302 x M16510.70
SCSS-190200-8007.48 - 7.8731.5017.9418.8931.503.5410.246.302 x M16617.08

Technical Illustration