EN RU CN

Product Finder

Our Product Finder tool allows you to find the perfect product for your requirements.

оронавирус COVID–19: Информация для клиентов касательно коронавируса COVID-19

Triton CDS (T3CDS-US) | Class I, Div 2 | AEx e, AEx d, AEx nR, AEx ta | Hazardous Location Cable GlandFor all types of Armoured Cables

Triton CDS Globally Approved, Hazardous (Classified) Location Cable Gland

• Fully sequential, three step installation procedure
• Reduces installation times, cost & risk
• Direct & remote installation
• Unique compensating displacement seal system (CDS)
– Metal-to-metal installation every time regardless of cable diameter
• Designed to prevent Coldflow
• Integral protected deluge seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• -76˚F to 266˚F (standard), -4˚F to 392˚F (ThermEx option T3CDSHT)
• Class I Zone 1, 21 and Zone 2, 22 Class I Division 2 ABCD
• Globally marked, UL, cCSAus, IECEx & ATEX
• As standard in nickel plated brass with NPT thread form

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below.

Stepped (W) Cone is suitable for Single Wire Armour (SWA), or Aluminium Wire Armour (AWA) cables.

BS 6121:Part 1:1989, IEC 62444, EN 62444
Impact = Level 8, Retention = Class D
IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Category B (Category A when used with braid, tape or pliable wire armour cables)
CML 18ATEX1326X
CML 18ATEX4318X
II 2G,II 1D, Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da,
II 3G Ex nR IIC Gc, I M2, Ex d I Mb, Ex e I Mb
EN60079-0,1,7,15,31
IECEx CML 18.0183X
IECEx SIM 14.0007X
Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
IEC 60079-0,1,7,15,31
1310517
Class I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III,
Enclosure Type 3, 4 and 4X, Class I, Zone 1, AEx e II, AEx nR II
Class I, Div 2, Groups A,B,C and D, Class II, Div 2, Groups E,F and G, Class III,
Enclosure Type 3, 4 and 4X, Ex d IIC, Ex e IIC, Ex nR II
CAN/CSA-C22.2 No 0, 18, 25, 30, 94, 174, CAN/CSA-E60079-0, 1, 7, ANSI/UL 514B Ed 5, ANSI/UL 50 Ed 11, ANSI/UL 2225 Ed 4, UL60079-0,1,7
E200163
Class I, Zone 1, AEx e II
UL514B
TC RU C-GB.ГБ05.B00138
GYJ13.1141X , GYJ13.1283X
P444949
TÜV 11.0374X
03866
LRS: 01/00172 (E3), DNV: E-13848, ABS: 14-LD234401A-4-PDA
IP66, IP67 & IP68
DTS01 : 91
NEMA 4X**
Electroless Nickel Plated Brass, Copper Free (<0.4%) Aluminium, Stainless Steel
CMP SOLO LSF Halogen Free Thermoset Elastomer
Steel / Served Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY/SY), Wire Braid Armour (e.g. SWB)
Reversible Armour Cone & AnyWay Universal Clamping Ring
Inner Bedding Sealing Ring: Compensating Displacement Seal (CDS), Outer
Sheath Sealing Ring : Load Retention Seal (LRS)
Cable Inner Bedding & Outer Cable Sheath

* Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings

Certificates

Click here to view Certificates

Product Selection Table

Click here to view Technical Illustration

Technical Illustration

Click here to view how to order

Cable Gland SizeAvailable Entry Threads "“C"” (Alternate Metric Thread Lengths Available)Thread Length
(NPT) “"E”"
Cable Bedding Diameter
“"A”"
Overall Cable Diameter "“B"”Armour RangeAcross Flats "“D"”Across Corners "D”"Protrusion
Length “"F”"
Combined Ordering Reference
(Nickel Plated Brass NPT)
ShroudCable
Gland
Weight
(ozs)
Standard† Grooved Cone (X)Stepped Cone (W)
NPTNPT (Option)Metric (Option)MinMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20s161/2”"3/4"M200.780.120.340.240.520.010.040.030.050.951.043.1020S16T3CDS1RA531PVC367.06
20S1/2”"3/4”"M200.780.240.460.370.630.010.040.030.050.951.043.1020ST3CDS1RA531PVC366.91
201/2”"3/4”"M200.780.260.550.490.820.020.040.030.051.201.323.0020T3CDS1RA531PVC069.77
25S3/4”"1”"M250.800.440.780.550.870.020.040.050.061.481.623.5025ST3CDS1RA532PVC0915.34
253/4”"1”"M250.800.440.780.721.030.020.050.050.061.481.623.4925T3CDS1RA532PVC0915.34
321”"1 1/4”"M320.980.671.030.931.340.020.050.060.081.811.993.5732T3CDS1RA533PVC1122.33
401 1/4”"1 1/2”"M401.010.871.261.101.590.020.060.060.082.172.383.6740T3CDS1RA534PVC1531.92
50S1 1/2”"2”"M501.031.161.501.391.840.020.060.080.102.362.603.9650ST3CDS1RA535PVC1839.65
502”"2 1/2”"M501.061.401.731.592.090.020.060.080.102.763.044.1650T3CDS1RA536PVC2156.57
63S2”"2 1/2”"M631.061.581.971.802.340.020.060.080.102.953.244.0363ST3CDS1RA536PVC2361.10
632 1/2”"3”"M631.571.862.202.152.590.020.060.080.103.153.474.1563T3CDS1RA537PVC2562.72
75S2 1/2”"3”"M751.572.082.442.322.840.020.060.080.103.543.904.3575ST3CDS1RA537PVC2890.70
753”"3 1/2”"M751.632.332.672.633.090.020.060.100.123.944.334.7375T3CDS1RA538PVC30117.93
903 1/2”"4”"M901.692.623.093.003.560.030.060.120.164.534.985.4790T3CDS1RA539PVC32171.73
1003 1/2"4”"M751.692.993.583.393.990.030.060.120.165.005.505.05100T3CDS1RA5310LSF33175.28
1154”"5”"M751.733.393.854.004.340.030.060.120.165.435.986.35115T3CDS1RA5311LSF34272.35
1305”"6”"M901.843.824.524.344.850.030.060.120.166.006.806.82130T3CDS1RA5312LSF35344.37
Dimensions are displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads “"C”" (Alternate Metric Thread Lengths Available)Thread Length "“E”"Cable
Bedding
Diameter
"“A"”
Overall Cable Diameter "“B”"Armour RangeAcross Flats "“D”"Across Corners "“D”"Protrusion Length “"F”"Combined Ordering Reference
(Nickel Plated Brass NPT)
ShroudCable
Gland
Weight
(Kgs)
Standard† Grooved Cone (X)Stepped Cone (W)
NPTNPT (Option)Metric (Option)MinMaxMinMaxMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20s161/2”"3/4”"M2019.93.18.66.113.10.31.00.81.2524.026.478.720S16T3CDS1RA531PVC360.20
20S1/2”"3/4”"M2019.96.111.69.515.90.31.00.81.2524.026.478.720ST3CDS1RA531PVC360.20
201/2”"3/4”"M2019.96.513.912.520.90.41.00.81.2530.533.676.220T3CDS1RA531PVC060.28
25S3/4”"1”"M2520.211.119.914.022.00.41.21.251.637.541.388.825ST3CDS1RA532PVC090.44
253/4”"1”"M2520.211.119.918.226.20.41.21.251.637.541.388.725T3CDS1RA532PVC090.44
321”"1 1/4”"M3225.017.026.223.733.90.41.21.62.046.050.690.732T3CDS1RA533PVC110.63
401 1/4”"1 1/2”"M4025.622.032.127.940.40.41.61.62.055.060.593.240T3CDS1RA534PVC150.91
50S1 1/2”"2”"M5026.129.538.135.246.70.41.62.02.560.066.0100.750ST3CDS1RA535PVC181.12
502”"2 1/2”"M5026.935.644.040.453.00.61.62.02.570.177.1105.850T3CDS1RA536PVC211.60
63S2”"2 1/2”"M6326.940.149.945.659.40.61.62.02.575.082.5102.563ST3CDS1RA536PVC231.73
632 1/2”"3”"M6339.947.255.954.665.80.61.62.02.580.088.0105.463T3CDS1RA537PVC251.78
75S2 1/2”"3”"M7539.952.861.959.072.00.61.62.02.590.099.0110.675ST3CDS1RA537PVC282.57
753”"3 1/2”"M7541.559.167.966.778.40.61.62.53.0100.0110.0120.375T3CDS1RA538PVC303.33
903 1/2”"4”"M9042.866.678.676.290.30.81.63.154.0115.0126.5138.990T3CDS1RA539PVC324.87
1003 1/2”"4”"M7542.876.090.986.1101.40.81.63.154.0127.0139.7128.2100T3CDS1RA5310LSF334.97
1154”"5”"M7544.086.097.9101.5110.20.81.63.154.0138.0151.8161.3115T3CDS1RA5311LSF347.72
1305”"6”"M9046.897.0114.9110.2123.20.81.63.154.0157.0172.7173.3130T3CDS1RA5312LSF359.78
Dimensions are displayed in millimeters unless otherwise stated