Cyclone III Heavy Duty 3 Strap Cable Cleat with Stainless Steel Base

The Cyclone III Strap cable cleats are metallic cable cleats consisting of a fabricated 316L stainless steel base and a stainless steel strap which have been designed, constructed, and tested in accordance with the International Standard ‘cable cleats for Electrical Installations’ IEC 61914. The Cyclone III Strap cable cleats ensure the retention and securing of cables, whilst preventing damage to the cable when in normal operation or in the event a short circuit fault condition.

The cable cleats allow a wide range of applications including miscellaneous formations. They have an exceptional overlapping range and give the end user more flexibility when compared to more rigid cable cleats on the market. Each cable cleat is capable of securing various cable
formations, such as single cable (multicore) or single cable in parallel formation, trefoil formation, and quad formation. Suitable for single cable applications diameters from 36mm to 165mm in 10 sizes, in trefoil formation from diameters of 24mm to 145mm in 15 sizes and quad formation from 21mm to 124mm in 15 sizes.

The Cyclone III Strap cable cleat is designed and tested to restrain cables securely during high short circuit forces and its straps wrap around the cables three times to provide the resistance needed.

The Cyclone III base is manufactured from 316L stainless steel, giving the cable cleats high creep strength and excellent corrosion resistance. The Cyclone straps are manufactured in 316L stainless steel providing excellent corrosion resistance, and the tensioned straps act as a coil during short circuit conditions to restrain the cable. The Cyclone strap wraps around the angled Cyclone III stainless steel base ensuring the cables are always kept central, the strap is fastened to a stainless steel pin with a hexagon shaped head at one end allowing fast, easy installation via the use of a ratchet, power tool or other suitable mechanical device.

The Cyclone III Strap cable cleats have one M12 and two M10 fixing clearance holes within the base, allowing versatile installation, and enabling the product to be secured to a variety of mounting surfaces. Due to the design of the Cyclone, the cables do not need to be lifted and placed in to the cable cleat, instead the cables are placed on to the bases and the Cyclone straps then wrap around the cables securing them to the mounting surface of the base.

The Cyclone III cable cleats and Cyclone intermediate straps come with standard liners, which are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus free. A high temperature version of the liner is available by adding HT suffix to the ordering code. The liners help to restrain the cables within vertical applications, providing a layer of protection between the cable sheath and the Cyclone stainless steel strap and base during normal operation where thermal elongation of cables occurs. The liners also prevent the cable from chafing on any mounting surface due to differential movements such as those found in marine and offshore applications, and protect the cable during short circuit conditions.

The Cyclone Straps are designed to be used as an intermediate restraint (where applicable) between two Cyclone cable cleats to bind cables together giving a cost effective, easy application fixing system. Using the Cyclone II and the Cyclone Intermediate Restraints alternatively will dramatically reduce installation time and cost, when compared to alternative cable cleat only solutions.

Features 

  • Third party certification to IEC 61914
  • 316L stainless steel base with stainless steel strap
  • Short circuit rating of 180kA peak fault
  • Standard operating temperature -50°C to +40°C
  • Standard liners are LUL approved and are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free
  • High temperature liner version with HT suffix available with operating temperature -50°C to +90°C
  • High temperature liners are classified as V0 Flame Retardant Polymer
  • Combined single (M12) and two bolt (M10) base fixing design

Patents granted: AU 2012307291, CN 201280044723.0, DE 2571125, SP 2571125, FR 2571125, HU 2571125, IT 2571125, KR 1663493, NL 2571125, NO 2571125, SG 11201400298Q, TR 2571125, GB 2571125, US 9353892

Cyclone III Short Circuit Testing to IEC 61914 - Clause 9.5
Trefoil Formation
One short circuit One short circuit w/ Cyclone strap Two short circuits Two short circuits w/ Cyclone strap
fixed cleat centres 300mm 300mm 600mm 1200mm 600mm 600mm 1200mm
0.1 sec 1 sec 1 sec 0.1 sec 0.1 sec 1 sec 0.1 sec
180kA Peak 90kA Peak 80kA Peak 137kA Peak 135kA Peak 75kA Peak 130kA Peak
81.8kA RMS 41.7kA RMS 36.9kA RMS 62.2kA RMS 61.4kA RMS 34.7kA RMS 60kA RMS
300mm 1 Cyclone III (0.1 sec)
Cable OD (mm)Peak kA
36180.0
38184.9
43196.7
59230.4
65241.9
Type 6.1.3 Composite Strap Cable Cleat - 2 Loop Cyclone II / 3 Loop Cyclone III
Design Specification IEC 61914
Temperature for permanent application -50 to +60°C
IEC 61914 clause / part 6.2
Needle Flame Test Pass - 120 second flame application time, IEC 61914 clause 10.0, 10.1, IEC 60695-11-5
Lateral Load Test Single - 6.5kN - 22kN Cyclone III, IEC 61914 clause 9.3
Trefoil - Refer to CMP Products, Cyclone III, IEC 61914 clause 9.3
Axial Load Test IEC 61914 clause 9.4, Single - 0.4kN Cyclone III
IEC 61914 clause 9.4, Trefoil - 0.4kN Cyclone III
Impact Resistance Very Heavy, IEC 61914 clause 6.3, 6.3.5, 9.2
Material 316L Stainless Steel Base & Strap
Standard liners are classified as Low Smoke & Fume (LSF), Zero Halogen (LS0H) and Phosphorus Free. HT liners are classified as V0 Flame Retardant Polymer

Note: The Cyclone III cable cleat consists of one base and one strap, additional cable straps (restraints) ordered separately. Coatings are available upon request by adding the following suffixes to the ordering reference – EC for epoxy coating, PC for polyester coating and TC for thermoplastic coating. Order reference example for epoxy coating of cable cleat base suffix EC (2CYC024034EC). Order reference example for high temperature liner version suffix HT (2CYC024034HT). Fasteners required to secure the cable cleat to the support structure are not included but can be supplied upon request. Isolation/separation pads (to prevent corrosion between two dissimilar metals) are not included but can be supplied on request - see isolation / seperation page.

Jump to technical illustration    Fixing Pack Information

Product Selection Table

Cyclone II Part No.Cyclone III Part No.Cable Ø Range Take (in.)Dimensions (in.)Weight
(oz)
SingleTrefoilQuadWHDPFixing Hole Ø
D1D2
2CYC0240343CYC0240341.417 - 1.9690.945 - 1.339 0.827 - 1.142 4.2523.7803.5043.1502 x M101 x M1218.31
2CYC0300413CYC0300411.772 - 2.362 1.181 - 1.614 1.024 - 1.378 4.2524.2913.5043.1502 x M101 x M1218.98
2CYC0370473CYC0370472.165 - 2.717 1.457 - 1.850 1.260 - 1.575 5.0394.7243.5043.9372 x M101 x M1221.59
2CYC0430543CYC0430542.520 - 3.150 1.693 - 2.126 1.457 - 1.811 5.0395.2763.5043.9372 x M101 x M1222.36
2CYC0500603CYC0500602.953 - 3.465 1.969 - 2.362 1.693 - 2.008 5.8275.7093.5044.7242 x M101 x M1225.71
2CYC0560673CYC0560673.268 - 3.898 2.205 - 2.638 1.929 - 2.244 5.8276.2203.5044.7242 x M101 x M1226.35
2CYC0630733CYC0630733.701 - 4.252 2.480 - 2.874 2.165 - 2.441 6.6146.6933.5045.5122 x M101 x M1229.00
2CYC0690803CYC0690804.055 - 4.646 2.717 - 3.150 2.362 - 2.677 6.6147.2053.5045.5122 x M101 x M1229.67
2CYC0720853CYC0720852.835 - 3.346 2.598 - 2.8347.4027.5983.5046.2992 x M101 x M1233.55
2CYC0820953CYC0820953.228 - 3.740 2.755 - 3.1887.4028.3463.5046.2992 x M101 x M1234.50
2CYC0921053CYC0921053.622 - 4.134 2.755 - 3.1888.2689.0943.5043.9372 x M101 x M1237.07
2CYC1021153CYC1021154.016 - 4.528 3.464 - 3.8588.2689.8433.5043.9372 x M101 x M1238.10
2CYC1121253CYC1121254.409 - 4.921 3.779 - 4.2129.25210.5913.5043.9372 x M101 x M1242.68
2CYC1221353CYC1221354.803 - 5.315 4.133 - 4.5669.25211.3393.5043.9372 x M101 x M1243.70
2CYC1321453CYC1321455.197 - 5.709 4.448 - 4.8819.84312.0873.5044.7242 x M101 x M1246.35
Cyclone III Part No.Cable Ø Range Take (mm)Dimensions mmWeight
(g)
SingleTrefoilQuadWHDPFixing Hole Ø
D1D2
3CYC02403436-5024-3421-291089689802 x M101 x M12519
3CYC03004145-6030-4126-3510810989802 x M101 x M12538
3CYC03704755-6937-4732-40128120891002 x M101 x M12612
3CYC04305464-8043-5437-46128134891002 x M101 x M12634
3CYC05006075-8850-6043-51148145891202 x M101 x M12729
3CYC05606783-9956-6749-57148158891202 x M101 x M12747
3CYC06307394-10863-7355-62168170891402 x M101 x M12822
3CYC069080103-11869-8060-68168183891402 x M101 x M12841
3CYC07208572-8566-72188193891602 x M101 x M12951
3CYC08209582-9570-81188212891602 x M101 x M12978
3CYC09210592-10570-81210231891002 x M101 x M121051
3CYC102115102-11588-98210250891002 x M101 x M121080
3CYC112125112-12596-107235269891002 x M101 x M121210
3CYC122135122-135105-116235288891002 x M101 x M121239
3CYC132145132-145113-124250307891202 x M101 x M121314

Technical Illustration