PXRC Cable Gland

Brass

Click thumbnails for alternate materials

logos

PXRC Tri-Star Flameproof Ex d & Increased Safety Ex e Conduit Connection Compound Barrier Cable Gland


CMP Type PXRC Certified Flameproof (Type 'd'), Increased Safety (Type 'e') indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all types of unarmoured cable housed in conduit systems. The cable gland provides a compound barrier seal around the cable conductors and is equipped with a rotating female connection for ease of conduit installation.

All CMP Cable Connectors are EMC Tested.

Click for more details

The cable gland provides mechanical cable retention and electrical continuity for the metallic conduit.

The CMP PXRC Conduit Connection Cable Gland is suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2 , Zone 21 & Zone 22 provided always that the prevailing code of practice for selection and installation is observed, e.g. IEC 60079-14.

Cable Gland Selection Table

  • View Metric Table
  • View Imperial Table
Cable Gland Size Available Entry Threads “C” Minimum Thread Length “E” Standard Female Connection Thread Diameter Over Conductors “A” Number of Cores Overall Cable Diameter “B” Across Flats “D” Across Corners “D” Nominal Protrusion Length “F” Ordering Reference (Brass Metric) M X F # Cable Gland Weight (Kgs)
Standard Option
Metric NPT NPT Max Max Max
20 M20 1/2" 3/4" 15.0 1/2" 12.6 21.0 13.9 13.9 27.0 29.7 24.0 20PXRC1RA031 0.100
25 M25 3/4" 1” 15.0 3/4" 17.5 38.0 19.9 19.9 36.0 39.6 26.0 25PXRC1RA032 0.250
32 M32 1” 1 1/4" 29.7 1” 23.6 59 26.2 26.2 41.0 45.1 27.0 32PXRC1RA033 0.460
40 M40 1 1/4" 1 1/2" 15.0 1 1/4" 30.0 89 32.0 32.3 50.0 55.0 28.0 40PXRC1RA034 0.615
50S M50 1 1/2" 2” 15.0 1 1/2" 36.6 115 38.1 38.9 55.0 60.5 29.0 50SPXRC1RA035 0.710
50 M50 2” 2 1/2" 15.0 2” 41.0 115 44.2 44.2 60.0 66.0 30.0 50PXRC1RA036 0.700
63S M63 2” 2 1/2" 15.0 2” 47.9 140 50.0 50.0 70.0 77.0 30.0 63SPXRC1RA036 0.850
63 M63 2 1/2" 3” 15.0 2 1/2" 53.7 140 56.0 58.0 75.0 82.5 30.0 63PXRC1RA037 0.820
75S M75 2 1/2" 3” 15.0 2 1/2" 59.9 140.0 62.4 62.4 79.0 86.9 32.0 75SPXRC1RA037 1.100
75 M75 3” 3 1/2" 15.0 3” 64.3 140.0 68.1 68.1 84.0 92.4 32.0 75PXRC1RA038 1.090
90 M90 3” 3 1/2" 15.0 3” 75.3 140.0 79.9 80.1 108.0 118.8 44.0 90PXRC1RA038 1.500
All dimensions in millimeters unless otherwise stated

Note: Please specify male and female connection threads required when ordering. # Other thread forms are available

Note: Please specify male and female connection threads required when ordering. # Other thread forms are available

TECHNICAL DATA
GOST R Certificate Number POCC GB.HO06.B00207
GOST R Code of Protection Category Ex d IIC / Ex e II / DIP A21
GOST R Compliance Standards ГOCT P 52350.0-2005, ГOCT P 52350.1-2005,
ГOCT P 52350.7-2005, ГOCT MЭK 61241-1-1-99
GOST GGTN Permit PPC 00-40706
GOST K Certificate Number KZ 75000361 01 01 14761
RoK Permit For Use Number 19-02-UL-1957
Lloyds Approval No. 01/00172
DNV Approval No. E-10496
ABS Approval No. 01-LD234401A/2-PDA
INMETRO Approval Certificate No. AEX-10786-X
INMETRO Code of Protection Category BR - Ex d IIC / BR - Ex e II - IP66
INMETRO Compliance Standards ABNT NBR IEC 60079-0:2006, ABNT NBR IEC 60079-1:2007, IEC 60079-7:2001 e ABNT NBR IEC 60529:2005
NEPSI Certificate Number GYJ081070
NEPSI Code of Protection Category Ex d IIC, Ex e II, Ex nR II, DIP A21 TA
NEPSI Compliance Standards GB3836.1/2/3-2000, GB3836.8-2003, GB12476.1-2000
RETIE Approval Number 03866
Type PXRC
ATEX Certification Detail SIRA06ATEX1097X
ATEX Code of Protection Category ATEX ATEX Approved II 2/3 GD Ex d IIC, Ex e II, Ex tD A21 IP66, - Equipment Zone 1, Zone 2, Zone 21, & Zone 22 - Gas Groups IIA, IIB, IIC
ATEX Compliance Standards EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1
IEC Ex Approval Number IECEx SIR 06.0044X
IEC ExCode of Protection Category Ex d IIC, Ex e II, Ex tD A21 IP66
IEC Ex Compliance Standards IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1
Continuous Operating Temperature -60°C to +100°C
Ingress Protection Rating IP66
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium, Stainless Steel
Seal Material Epoxy Resin Barrier Compound
Material Safety Data Sheet Hardener / Resin
Cable Type Unarmoured
Sealing Area(s) Inner Compound Barrier
Optional Accessories Adaptor/Reducer, Earth Tag, Locknut, Serrated Washer, Entry Thread Seal, Shroud