Product Finder

Product Finder

Our Product Finder tool allows you to find the perfect product for your requirements.

CX | Industrial Cable GlandFor Braid, Pliable Wire & Steel Tape Armoured Cables

Single Seal Industrial Cable Gland

• High quality durable materials
• Robust, heavy duty design
• Metal-to-metal armour clamping
• Direct & remote installation
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• -60˚C to +130˚C (standard), -20˚C to 200˚C (ThermIn option CXHT)
• Deluge protection option
• EMC tested

† Grooved Cone (X) is predominantly used for Wire Braid (e.g. GSWB, TCWB), Steel Tape Armour (STA, DSTA) and Aluminium Strip Armour (ASA) but is also suitable for Single Wire Armour (SWA), Aluminium Wire Armour (AWA) and Pliable Wire Armour (PWA) if the range is outside that of the Stepped Cone (W).

Note: Grooved Cone (X) dimensions shown in the Cable Gland Selection Table below are for a double wire strand of braid armour cables. Tapes can also be doubled over. For cables that have only a single layer of armour such as SWA the clamping range should be used as shown in the table below

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications * Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category A
GOST R Certificate POCC GB.ГБ05.H00187
Marine Approvals LRS: 01/00171 (E1), ABS: 16-LD1472056-PDA
Ingress Protection Rating ** IP66 as standard (IP67, IP68 available upon request)
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP Thermoset Rubber
Cable Type Wire Braid Armour, Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Pliable Wire Armour (PWA), Steel Tape Armour (STA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique Unique CMP ‘LRS’ Outer Seal (Load Retention Seal)
Sealing Area(s) Cable Outer Sheath
Cable Gland Kits Available Cable Gland kit for use with all types of cable includes 2 Brass Cable Glands, 2 Steel Locknuts, 2 Brass Earth Tags and 2 PVC Shrouds for sizes up to and including 32mm. For sizes 40mm and above each kit includes 1 of each component.
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings

Introducing the Sentinel

Certificates

Click here to view Certificates

Product Selection Table

Click here to view Technical Illustration

Technical Illustration

Click here to view how to order

Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats “D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
MetricThread Length
(Metric) “E”
MaxMaxMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M200.390.340.240.520.010.040.941.041.8920S16CX1RAPVC043.53
20SM200.390.460.370.630.010.040.941.041.8920SCX1RAPVC043.53
20M200.390.550.490.820.020.041.201.321.8920CX1RAPVC065.19
25SM250.390.790.550.870.020.051.481.632.2025SCX1RAPVC097.90
25M250.390.790.721.030.020.051.481.632.2025CX1RAPVC097.80
32M320.391.040.931.330.020.051.811.992.1332CX1RAPVC1110.79
40M400.591.271.101.590.020.062.172.382.2840CX1RAPVC1515.80
50SM500.591.501.391.840.020.062.362.602.4050SCX1RAPVC1820.00
50M500.591.741.592.090.020.062.763.042.3650CX1RAPVC2126.49
63SM630.591.971.802.340.020.062.953.252.9163SCX1RAPVC2336.54
63M630.592.202.152.590.020.063.153.462.8063CX1RAPVC2535.84
75SM750.592.442.322.830.020.063.543.903.3975SCX1RAPVC2863.03
75M750.592.682.633.090.020.063.944.333.2375CX1RAPVC3073.76
90M900.943.153.003.560.030.064.504.953.7490CX1RAPVC32107.37
100M1000.943.583.393.990.030.064.845.333.74100CX1RALSF33110.48
115M1150.943.864.004.340.030.065.255.784.23115CX1RALSF34157.89
130M1300.944.534.344.850.030.066.006.604.33130CX1RALSF35203.21
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats “D”
Across
Corners
“D”
Protrusion
Length “F”
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
MetricThread Length
(Metric) “E”
MaxMaxMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M2010.08.76.113.10.31.024.026.448.020S16CX1RAPVC040.10
20SM2010.011.79.515.90.31.024.026.448.020SCX1RAPVC040.10
20M2010.014.012.520.90.41.030.533.648.020CX1RAPVC060.15
25SM2510.020.014.022.00.41.237.541.356.025SCX1RAPVC090.22
25M2510.020.018.226.20.41.237.541.356.025CX1RAPVC090.22
32M3210.026.323.733.90.41.246.050.654.032CX1RAPVC110.31
40M4015.032.227.940.40.41.655.060.558.040CX1RAPVC150.45
50SM5015.038.235.246.70.41.660.066.061.050SCX1RAPVC180.57
50M5015.044.140.453.00.61.670.177.160.050CX1RAPVC210.75
63SM6315.050.045.659.40.61.675.082.574.063SCX1RAPVC231.04
63M6315.056.054.665.80.61.680.088.071.063CX1RAPVC251.02
75SM7515.062.059.072.00.61.690.099.086.075SCX1RAPVC281.79
75M7515.068.066.778.40.61.6100.0110.082.075CX1RAPVC302.09
90M9024.080.076.290.30.81.6114.3125.795.090CX1RAPVC323.04
100M10024.091.086.1101.40.81.6123.0135.395.0100CX1RALSF333.13
115M11524.098.0101.5110.20.81.6133.4146.7107.5115CX1RALSF344.48
130M13024.0115.0110.2123.20.81.6152.4167.6110.0130CX1RALSF355.76
Dimensions displayed in millimeters unless otherwise stated