Product Finder

Product Finder

Our Product Finder tool allows you to find the perfect product for your requirements.

BW SOLO | Industrial Cable GlandFor all types of Steel & Aluminium Wire Armoured Cables

BW Industrial Cable Gland SOLO LSF Kit

• Direct & remote installation
• -60˚C to +200˚C
• EMC tested
• LUL (London Underground) approved

Note: Ordering suffix ‘2RA’ includes locknut, earth tag & shroud

Other kit options available

 

Type BW SOLO-Kit
Design Specification BS 6121:Part 1:1989
Mechanical Classifications * Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications * Category B
GOST R Certificate POCC GB.ГБ05.H00187
Marine Approvals LRS: 01/00171 (E1), ABS: 16-LD1472056-PDA
Ingress Protection Rating ** IP2X
Cable Gland Material Brass, Electroless Nickel Plated Brass
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA)
Armour Clamping Two Part Armour Lock
Cable Gland Kits Available Up to & including size 25 - 2 glands, 2 locknuts, 2 earth tags & 2 LSF shrouds
Size 32 & above - 1 gland, 1 locknut, 1 earth tag & 1 LSF shroud
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners, Armour Former Tool

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings

As IEC 62444 and EN 62444 do not cover cable glands which are supplied without cable sealing rings, the information provided here is for information only.

Introducing the Sentinel

Certificates

Click here to view Certificates

Product Selection Table

Click here to view Technical Illustration

Technical Illustration

Click here to view how to order

Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats “D”
Across
Corners
“D”
Protrusion
Length “F” (Without Shroud)
Combined Ordering Reference
(*Brass Metric)
Cable
Gland
Only
Weight
(Ozs)
StandardMaxMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
MetricThread Length
(Metric) “E”
20SM200.390.460.620.030.050.870.950.7320SBWLSF2RA1.83
20M200.390.550.830.030.051.101.210.8920BWLSF2RA3.10
25M250.390.791.070.050.061.301.430.8525BWLSF2RA3.88
32M320.391.041.340.060.081.611.780.8932BWLSF2RA5.26
40M400.591.271.670.060.081.972.171.1840BWLSF2RA11.15
50SM500.591.501.970.080.102.252.471.1850SBWLSF2RA16.51
50M500.591.742.190.080.102.562.811.2650BWLSF2RA16.83
63SM630.591.972.460.080.102.953.251.6363SBWLSF2RA22.29
63M630.592.202.690.080.103.113.421.6363BWLSF2RA31.39
75SM750.592.443.020.080.103.503.851.8775SBWLSF2RA44.73
75M750.592.683.260.100.123.744.111.9575BWLSF2RA49.38
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads “C” (Alternate Metric Thread Lengths Available)Cable
Bedding
Diameter
“A”
Overall
Cable
Diameter
“B”
Armour RangeAcross
Flats “D”
Across
Corners
“D”
Protrusion
Length “F”
(Without Shroud)
Combined Ordering Reference
(*Brass Metric)
Cable
Gland Only
Weight
(Kgs)
Standard
MetricThread Length
(Metric) “E”
MaxMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20SM2010.011.715.80.81.2522.024.218.520SBWLSF2RA0.05
20M2010.014.021.10.81.2528.030.822.520BWLSF2RA0.09
25M2510.020.027.21.251.633.036.321.525BWLSF2RA0.11
32M3210.026.334.11.62.041.045.122.532BWLSF2RA0.15
40M4015.032.242.41.62.050.055.030.040BWLSF2RA0.32
50SM5015.038.250.12.02.557.162.830.050SBWLSF2RA0.47
50M5015.044.155.72.02.565.071.532.050BWLSF2RA0.48
63SM6315.050.062.42.02.575.082.541.363SBWLSF2RA0.63
63M6315.056.068.22.02.579.086.941.363BWLSF2RA0.89
75SM7515.062.076.82.02.589.097.947.675SBWLSF2RA1.27
75M7515.068.082.92.53.095.0104.549.675BWLSF2RA1.40
Dimensions displayed in millimeters unless otherwise stated