CMP E1W CIEL type brass cable gland for use with all types of Single Wire Armour (SWA) cable providing an environmental seal on the cable Inner bedding and outer cable sheath, mechanical retention and electrical continuity via armour wire termination.

All CMP Cable Glands are EMC Tested.

More +

Less -

The CMP E1W CIEL range of industrial cable glands is designed and tested to BS 6121:Part 1:1989, meets or surpasses the requirements of EN 50262 :1999, and is produced from Brass grade CuZn39Pb3 (CW614N) to EN12168.

The E1W CIEL cable gland is complete with a CMP unique Cast Integral Earth Lug concept. This is particularly suitable for use with Medium and High Voltage systems where a high level of protection against short circuit earth fault currents is required.

Cable Gland Selection Table

  • View Metric Table
  • View Imperial Table
Cable Gland Size Available Entry Threads "C" Minimum Thread Length "E" Cable Bedding Diameter "A" Overall Cable Diameter "B" Armour Range Across Flats "D" Across Corners "D" Protrusion Length "F" CIEL Earth Bolt Size Earth Fault Current Rating (kA) Ordering Reference (Brass Metric) Cable Gland Weight (Kgs)
Standard Option Min Max Min Max Min Max Max Max
Metric NPT NPT
20S M20 1/2" 3/4" 10.0 6.1 11.6 9.5 15.9 0.8 1.25 24.0 26.4 58.5 M8 26 20SE1WC1RA 0.142
20 M20 1/2" 3/4" 10.0 6.5 13.9 12.5 20.9 0.8 1.25 30.5 33.6 60.5 M8 26 20E1WC1RA 0.230
25S M25 3/4" 1" 10.0 11.1 19.9 14.0 22.0 1.25 1.6 37.5 41.3 67.5 M8 26 25SE1WC1RA 0.328
25 M25 3/4" 1" 10.0 11.1 19.9 18.2 26.2 1.25 1.6 37.5 41.3 67.5 M8 26 25E1WC1RA 0.328
32 M32 1" 1 1/4" 10.0 17.0 26.2 23.7 33.9 1.6 2.0 46.0 50.6 69.5 M8 26 32E1WC1RA 0.470
40 M40 1 1/4" 1 1/2" 15.0 22.0 32.1 27.9 40.4 1.6 2.0 55.0 60.5 78.0 M10 26 40E1WC1RA 0.780
50S M50 1 1/2" 2" 15.0 29.5 38.1 35.2 46.7 2.0 2.5 60.0 66.0 75.5 M12 43 50SE1WC1RA 0.960
50 M50 2" 2 1/2" 15.0 35.6 44.0 40.4 53.1 2.0 2.5 70.0 77.0 80.5 M12 43 50E1WC1RA 1.150
63S M63 2" 2 1/2" 15.0 40.1 49.9 45.6 59.4 2.0 2.5 75.0 82.5 91.5 M12 43 63SE1WC1RA 1.700
63 M63 2 1/2" 3" 15.0 47.2 55.9 54.6 65.9 2.0 2.5 80.0 88.0 92.0 M12 43 63E1WC1RA 1.650
75S M75 2 1/2" 3" 15.0 52.8 61.9 59.0 72.1 2.0 2.5 89.0 97.9 99.0 M12 43 75SE1WC1RA 2.600
75 M75 3" 3 1/2" 15.0 59.1 67.9 66.7 78.5 2.5 3.0 99.0 108.9 102.0 M12 43 75E1WC1RA 3.300
90 M90 3" 3 1/2" 15.0 66.6 79.9 76.2 90.4 3.0 3.5 114.0 125.4 120.0 M12 43 90E1WC1RA 4.850
100 M100 4" - 15.0 76.0 90.9 86.1 101.5 3.15 4.0 123.0 135.3 138.0 M12 43 100E1WC1RA 5.950
Dimensions are displayed in Millimetres

NOTE: *CMP SOLO LSF Halogen Free Shrouds also available on request. + Alternative armour clamping range available for non-standard armour sizes. # Other thread forms are available

NOTE: *CMP SOLO LSF Halogen Free Shrouds also available on request. + Alternative armour clamping range available for non-standard armour sizes. # Other thread forms are available

TECHNICAL DATA
GOST R Certificate Number POCC GB.06.H00187
GOST GGTN Permit PPC 00-40706
GOST K Certificate Number KZ 75000361 01 01 14761
RoK Permit For Use Number 19-02-UL-1957
Type E1W CIEL
Design Specification BS 6121:Part 1:1989, EN 50262:1999, IEC 62444:2010
Continuous Operating Temperature -60°C to +150°C
Ingress Protection Rating IP66
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium, Stainless Steel
Seal Material CMP Formulated Thermoplastic Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP "LRS" TM Outer Load Retention Seal
Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Accessories Adaptor/Reducer, Locknut, Serrated Washer, Entry Thread Seal, Shroud

EN 50262 Mechanical Classifications - Retention = Class B, Impact = Level 8

EN 50262 Electrical Classifications - Category C

The Symmetrical Fault Current (kA) rating for 1 second applicable to the Cast Integral Earth Lug featured in the E1W CIEL products are as follows:-
26.0 kA for cable gland sizes up to 40
43.0 kA for cable gland sizes 50S and above