CW CIEL Cable Gland

Brass

Click thumbnails for alternate materials

CW CIEL Heavy Duty Industrial Cable Gland

CMP CW CIEL type brass cable gland for use with all types of Single Wire Armour (SWA) cable providing an environmental seal on the cable outer sheath, mechanical retention and electrical continuity via armour wire termination.

All CMP Cable Glands are EMC Tested.

More +

Less -

The CMP CW CIEL range of industrial cable glands is designed and tested to BS 6121:Part 1:1989, meets or surpasses the requirements of EN 50262 :1999, and is produced from Brass grade CuZn39Pb3 (CW614N) to EN12168.

The CW CIEL cable gland is complete with a CMP unique Cast Integral Earth Lug concept. This is particularly suitable for use with Medium and High Voltage systems where a high level of protection against short circuit earth fault currents is required.

Cable Gland Selection Table

  • View Metric Table
  • View Imperial Table
Cable Gland Size Entry Thread "C" Minimum Thread Length "E" Cable Bedding Diameter "A" Overall Cable Diameter "B" Armour Range Across Flats "D" Across Corners "D" Protrusion Length "F" CIEL Earth Bolt Size Earth Fault Current Rating (kA) Ordering Reference (Brass Metric) Shroud Ref * Cable Gland Weight (Kgs)
Max Min Max Min Max Max Max
20S M20 10.0 11.6 9.5 15.9 0.8 1.3 24.0 26.4 58.5 M8 26.0 20SCWC1RA PVC04 0.140
20 M20 10.0 13.9 12.5 20.9 0.8 1.3 30.5 33.6 60.5 M8 26.0 20CWC1RA PVC06 0.180
25S M25 10.0 19.9 14.0 22.0 1.3 1.6 36.0 39.6 67.5 M8 26.0 25SCWC1RA PVC09 0.257
25 M25 10.0 19.9 18.2 26.2 1.3 1.6 36.0 39.6 67.5 M8 26.0 25CWC1RA PVC09 0.257
32 M32 10.0 26.2 23.7 33.9 1.6 2.0 46.0 50.6 69.5 M8 26.0 32CWC1RA PVC11 0.376
40 M40 15.0 32.1 27.9 40.4 1.6 2.0 55.0 60.5 78.0 M10 26.0 40CWC1RA PVC15 0.630
50S M50 15.0 38.1 35.2 46.7 2.0 2.5 60.0 66.0 75.5 M12 43.0 50SCWC1RA PVC18 0.757
50 M50 15.0 44.0 40.4 53.1 2.0 2.5 70.1 77.1 80.5 M12 43.0 50CWC1RA PVC21 0.862
63S M63 15.0 49.9 45.6 59.4 2.0 2.5 75.0 82.5 91.5 M12 43.0 63SCWC1RA PVC23 1.390
63 M63 15.0 55.9 54.6 65.9 2.0 2.5 80.0 88.0 92.0 M12 43.0 63CWC1RA PVC25 1.360
75S M75 15.0 61.9 59.0 72.1 2.0 2.5 90.0 99.0 99.0 M12 43.0 75SCWC1RA PVC28 2.307
75 M75 15.0 67.9 66.7 78.5 2.5 3.0 100.0 110.0 102.0 M12 43.0 75CWC1RA PVC30 2.909
90 M90 15.0 79.9 76.2 90.4 3.15 3.15 114.0 125.4 120.0 M12 43.0 90CWC1RA PVC32 3.858
100 M100 15.0 90.9 86.1 101.5 3.15 4.0 123.0 135.3 150.0 M12 43.0 100CWC1RA LSF33 4.958
115 M115 15.0 97.9 101.3 110.3 3.15 4.0 133.4 146.7 170.0 M12 43.0 115CWC1RA LSF34 5.053
130 M130 15.0 114.9 114.0 123.3 3.15 4.0 152.4 167.6 180.0 M12 43.0 130CWC1RA LSF35 6.158
Dimensions are displayed in millimetres unless otherwise stated

NOTE: * CMP SOLO LSF Halogen Free Shrouds also available on request. # Please click on the "How To Order" page above for information on other thread forms, materials and finishes.

NOTE: * CMP SOLO LSF Halogen Free Shrouds also available on request. # Please click on the "How To Order" page above for information on other thread forms, materials and finishes.

TECHNICAL DATA
GOST R Certificate Number POCC GB.06.H00187
GOST GGTN Permit PPC 00-40706
GOST K Certificate Number KZ 75000361 01 01 14761
RoK Permit For Use Number 19-02-UL-1957
Type CW CIEL
Design Specification BS 6121 :Part 1:2005, EN 50262:1999, IEC 62444:2010
Continuous Operating Temperature -60°C to +150°C
Ingress Protection Rating IP66
Ingress Protection Document 5046 C549H
Deluge Protection Compliance DTS01 : 91
Deluge Protection Document 5046 C549H-D
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP Formulated Thermoplastic Elastomer
Cable Type Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Steel Tape Armour (STA), Aluminium Strip Armour (ASA), Wire Braid Armour, Screened Flexible Wire Braid (e.g. CY / SY), Pliable Wire Armour (PWA)
Armour Clamping Reversible Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique Unique CMP "LRS" TM Outer Seal (Load Retention Seal)
Sealing Area(s) Cable Outer Sheath
Accessories Adaptor/Reducer, Earth Tag, Locknut, Serrated Washer, Entry Thread Seal, Shroud

EN 50262 Mechanical Classifications - Retention = Class B, Impact = Level 8

EN 50262 Electrical Classifications - Category C

The Symmetrical Fault Current (kA) rating for 1 second applicable to the Cast Integral Earth Lug featured in the CW CIEL products are as follows:-
26.0 kA for cable gland sizes up to 40
43.0 kA for cable gland sizes 50S and above.

Close [-]

Video Coming Soon

 

CMP WP CWCIEL_0311