A2F Cable Gland

Brass

Click thumbnails for alternate materials

logos

A2F Cable Gland, Flameproof Ex d, Increased Safety Ex e and Restricted Breathing Ex nR Cable Gland


CMP Type A2F Triple Certified Flameproof (Type 'd'), Increased Safety (Type 'e') and Restricted Breathing (Type ‘nR’) indoor and outdoor cable gland for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas with un-armoured and braided cable providing a combined flameproof seal and environmental seal on the cable outer sheath. This product provides full compatibility with restricted breathing equipment that rely upon flammable gases being excluded from the main enclosure.

All CMP Cable Glands are EMC Tested.

Click for more details

The CMP A2F Tri-Star Cable Gland is suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 & Zone 22 provided always that the prevailing code of practice for selection, installation and maintenance is observed, e.g. IEC 60079-14.

Cable Gland Selection Table

  • View Metric Table
  • View Imperial Table
Cable Gland Size
Available Entry Threads "C"
Minimum Thread Length "E"
Overall Cable Diameter "A"
Across Flats "D"
Across Corners "D"
Nominal Protrusion Length "F"
Ordering Reference (Brass Metric)#
Shroud Ref *
Cable Gland Weight (Kgs)

Standard

Option
Metric
NPT
NPT
Min
Max
Max
Max
16 M16 1/2" 3/4" 15.0 3.2 8.7 22.0 24.2 18.0 16A2F1RA PVC02 0.051
20S/16 M20 1/2" 3/4" 15.0 3.2 8.7 24.0 26.4 21.0 20S16A2F1RA PVC04 0.054
20S M20 1/2" 3/4" 15.0 6.1 11.7 24.0 26.4 21.0 20SA2F1RA PVC04 0.054
20 M20 1/2" 3/4" 15.0 6.5 14.0 27.0 29.7 24.0 20A2F1RA PVC05 0.059
25 M25 3/4" 1" 15.0 11.1 20.0 36.0 39.6 26.0 25A2F1RA PVC09 0.112
32 M32 1" 1 1/4" 15.0 17.0 26.3 41.0 45.1 27.0 32A2F1RA PVC10 0.128
40 M40 1 1/4" 1 1/2" 15.0 23.5 32.2 50.0 55.0 28.0 40A2F1RA PVC13 0.168
50S M50 1 1/2" 2" 15.0 31.0 38.2 55.0 60.5 29.0 50SA2F1RA PVC14 0.224
50 M50 2" 2 1/2" 15.0 35.6 44.1 60.0 66.0 30.0 50A2F1RA PVC17 0.231
63S M63 2" 2 1/2" 15.0 41.5 50.0 70.0 77.0 30.0 63SA2F1RA PVC20 0.360
63 M63 2 1/2" 3" 15.0 47.2 56.0 75.0 82.5 30.0 63A2F1RA PVC22 0.344
75S M75 2 1/2" 3" 15.0 54.0 62.0 79.0 86.9 32.0 75SA2F1RA PVC24 0.466
75 M75 3" 3 1/2" 15.0 61.1 68.0 84.0 92.4 32.0 75A2F1RA PVC26 0.395
90 M90 3" 3 1/2" 15.0 66.6 80.0 108.0 118.8 44.0 90A2F1RA PVC31 1.346
100 M100 4" - 15.0 76.0 91.0 122.0 134.2 48.0 100A2F1RA LSF32 1.575
115 M115 - - 15.0 86.0 98.0 138.0 151.8 55.0 115A2F1RA LSF34 2.322
130 M130 - - 15.0 97.0 115.0 154.0 169.4 62.0 130A2F1RA LSF35 3.400
All dimensions in millimeters

Note: CMP SOLO LSF Halogen Free Shrouds also available on request. IEC Ex, ATEX (Group I and II) & CSA hazardous area certification marking included as standard. Please consult CMP for any other requirement.

Note: CMP SOLO LSF Halogen Free Shrouds also available on request. IEC Ex, ATEX (Group I and II) & CSA hazardous area certification marking included as standard. Please consult CMP for any other requirement.

TECHNICAL DATA
CSA Approval Certificate No. 1211841
CSA Code of Protection Category Class 4418 05; Class I, Zone I, Class II, Div 2, Groups E,F,&G, Enclosure Type 3,4,&4X; Class III; Ex d IIC, Ex e II
CSA Compliance Standards CSA Standard C22.2 No 0. M1991, CSA Standard C22.2 No. 0.4-04, CSA Standard C22.2 No. 94-M91, CSA Standard C22.2 No. 174-M1984, CAN/CSA-E60079-0:07, CAN/CSA-E60079-1:07, CAN/CSA-E60079-7:01
GOST R Certificate Number POCC GB.HO06.B00207
GOST R Code of Protection Category Ex d IIC / Ex e II / DIP A21
GOST R Compliance Standards ГOCT P 52350.0-2005, ГOCT P 52350.1-2005,
ГOCT P 52350.7-2005, ГOCT MЭK 61241-1-1-99
GOST GGTN Permit PPC 00-40706
GOST K Certificate Number KZ 75000361 01 01 14761
RoK Permit For Use Number 19-02-UL-1957
Lloyds Approval No. 01/00172
DNV Approval No. E-10496
ABS Approval No. 01-LD234401A/2-PDA
INMETRO Approval Certificate Number. MC-AEX-7619-X
INMETRO Code of Protection Category BR-Ex d IIC / BR-Ex e II
INMETRO Compliance Standards IEC 60079-0/00, IEC 60079-1/01, IEC 60079-7/01, NBE IEC 60529/05
NEPSI Certificate Number GYJ081070
NEPSI Code of Protection Category Ex d IIC, Ex e II, Ex nR II, DIP A21 TA
NEPSI Compliance Standards GB3836.1/2/3-2000, GB3836.8-2003, GB12476.1-2000
RETIE Approval Number 03866
Type A2F
Design Specification BS 6121:Part 1:1989, EN 50262:1999
ATEX Certification Detail SIRA 06ATEX1097X, SIRA07ATEX4326X
ATEX Code of Protection Category ATEX ATEX Approved II 2 GD, Ex d IIC, Ex e II, Ex tD A21 IP66, ATEX ATEX Approved II 3 G Ex nR II, ATEX ATEX Approved IM2, Ex d I, Ex e I
ATEX Compliance Standards EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, IEC 61241-0, EN 61241-1
IEC Ex Certification Detail IECEx SIR 06.0039X
IEC Ex Code of Protection Category Ex d IIC, Ex e II, Ex nR II, Ex tD A21 IP66, Ex d I, Ex e I
IEC Ex Compliance Standards IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 60079-15, IEC 61241-0, IEC 61241-1
Continuous Operating Temperature -60°C to +130°C
Ingress Protection Rating IP66, IP67, IP68
Ingress Protection Document 5046 C549-D
Deluge Protection Compliance DTS01 : 91
Deluge Protection Document 5046 C549-D
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP SOLO LSF Thermoplastic Elastomer
Cable Type Unarmored & Braided
Sealing Technique CMP Unique Displacement Seal Concept
Sealing Area(s) Cable Outer Sheath
Accessories Adaptor/Reducer, Earth Tag, Locknut, Serrated Washer, Entry Thread Seal, Shroud


Additional information

Close [-]

If you cannot view this video please email us for details - webmaster@cmp-products.com

CMP WP A2F_0511