781 Series Breather/Drain Plugs

Click thumbnail for alternative images

logos

Breather / Drain Plug Type 781 with increased Safety Ex e II form of protection.


The CMP Type 781 Breather / Drain Plug is designed for Increased Safety Ex e apparatus that is susceptible to condensation or prone to moisture collection or ingress during normal operation. The Type 781 is designed to act as both a drainage device, when mounted in a bottom entry of the equipment, and also to enable the inside air to breathe with the external environment under normal ambient and atmospheric conditions, whilst excluding further dust and moisture from penetrating the enclosure. The Type 781 Breather / Drain Plug is supplied complete with an integral entry thread ‘O’ ring seal, and a castellated locknut to facilitate drainage from inside the enclosure. A General Purpose Industrial version is also available.

Metallic Breather / Drain Plugs are available in Brass, Aluminium or Stainless Steel and can be supplied for both Industrial and Hazardous Area applications, with Ex e Component Approval.

Thread forms available are metric sizes M20 and M25 and NPT equivalents.

Features:

  • Filter prevents any dirt or other foreign bodies from entering the enclosure
  • Breathing capabilities help to combat the build up of moisture and potential condensation in the apparatus.
  • Slotted Entry Threads and Castellated Locknut allows excess water to flow into inverted drain device.
  • Draining features enable release of any water that has penetrated the apparatus whilst maintaining the Increased Safety form of protection.
  • Integral ‘O’ Ring ensures an effective seal at the interface between the Breather/Drain device and the equipment.

781 Series Breather/Drain Plugs Table

  • View Metric Table
  • View Imperial Table
Ordering Reference Thread Size Minimum Thread Length Protrusion Height Across Flats Dimension Across Corners Dimensions Installation Torque (Nm)
781EM2 M20 x 1.5 15.0 17.0 30.0 33.0 7
781EM3 M25 x 1.5 15.0 17.0 31.5 34.7 10
781ET1 1/2" NPT 19.9 17.0 30.0 33.0 7
781ET2 3/4" NPT 20.2 17.0 31.5 34.7 10
Dimensions are displayed in millimetres unless otherwise stated

NOTE: Marked with ATEX, IECEx and cCSAus certification details as standard. Please refer to Ordering Guide Tables for reference definitions, denoting material variants.

NOTE: Marked with ATEX, IECEx and cCSAus certification details as standard. Please refer to Ordering Guide Tables for reference definitions, denoting material variants.

TECHNICAL DATA
cCSAus Approval Certificate No. 1055233
cCSAus Code of Protection Category Ex e II, Class I, Zone 1, AEx e II; IP66; Enclosure Type 4X
cCSAus Compliance Standards C22.2 No. 0.5-M1982, C22.2 No. 30-M1986, C22.2 No. 94-M1991,CAN/CSA E60079-0:07, CAN/CSA E60079-1:07,CAN/CSA E60079-7:02, UL Standard 50, Eleventh Edition, UL Standard 1203, Fourth Edition, UL 60079-0, Fourth Edition, UL 60079-1, Fifth Edition, UL 60079-7, First Edition
GOST R Certificate Number POCC GB.HO06.B00207
GOST R Code of Protection Category Ex e II
GOST R Compliance Standards ГOCT P 52350.0-2005, ГOCT P 52350.1-2005,
ГOCT P 52350.7-2005, ГOCT MЭK 61241-1-1-99
GOST GGTN Permit PPC 00-40706
GOST K Certificate Number KZ 75000361 01 01 14761
RoK Permit For Use Number 19-02-UL-1957
Lloyds Approval No. 01/00172
DNV Approval No. E-10496
ABS Approval No. 01-LD234401C/1-PDA
INMETRO Approval Certificate Number. AEX-13104-U
INMETRO Code of Protection Category BR-Ex e II
INMETRO Compliance Standards ABNT NBR IEC 60079-0:2006, IEC 60079-1:2007 e IEC 60079-2007:2001
RETIE Approval Number 03866
Type 781
Design Specification BS 6121:Part 1:1989
ATEX Certification Detail SIRA01ATEX1284U
ATEX Code of Protection Category ATEX ATEX Approved II 2 GD Ex e II Component, Zone 1, Zone 2, Zone 21, & Zone 22 - Gas Groups IIA, IIB, IIC
ATEX Compliance Standards EN 60079-0, EN 60079-1, EN 60079-7, EN 50281-1-1
IEC Ex Certification Detail IEC Ex SIR07.0054U
IEC Ex Code of Protection Category Ex e II, Ex tD A21 IP6X
IEC Ex Compliance Standards IEC 60079-0, IEC 60079-7, IEC 61241-0, IEC 61241-1
Continuous Operating Temperature -60°C to +60°C
Ingress Protection Rating IP66 (when fitted in a bottom entry, perpendicular manner)
Material Brass, Electroless Nickel Plated Brass, Aluminium, Stainless Steel

Accessories included - Integral Entry Thread "O" Ring Seal, Castellated Locknut

Additional information

CMP WP 781_0311