Breather / Drain Plug Type 781 with increased Safety Ex e II form of protection.
The CMP Type 781 Breather / Drain Plug is designed for Increased Safety Ex e apparatus that is susceptible to condensation or prone to moisture collection or ingress during normal operation. The Type 781 is designed to act as both a drainage device, when mounted in a bottom entry of the equipment, and also to enable the inside air to breathe with the external environment under normal ambient and atmospheric conditions, whilst excluding further dust and moisture from penetrating the enclosure. The Type 781 Breather / Drain Plug is supplied complete with an integral entry thread ‘O’ ring seal, and a castellated locknut to facilitate drainage from inside the enclosure. A General Purpose Industrial version is also available.
Metallic Breather / Drain Plugs are available in Brass, Aluminium or Stainless Steel and can be supplied for both Industrial and Hazardous Area applications, with Ex e Component Approval.
Thread forms available are metric sizes M20 and M25 and NPT equivalents.
Features:
- Filter prevents any dirt or other foreign bodies from entering the enclosure
- Breathing capabilities help to combat the build up of moisture and potential condensation in the apparatus.
- Slotted Entry Threads and Castellated Locknut allows excess water to flow into inverted drain device.
- Draining features enable release of any water that has penetrated the apparatus whilst maintaining the Increased Safety form of protection.
- Integral ‘O’ Ring ensures an effective seal at the interface between the Breather/Drain device and the equipment.
781 Series Breather/Drain Plugs Table
- View Metric Table
- View Imperial Table
| Ordering Reference | Thread Size | Minimum Thread Length | Protrusion Height | Across Flats Dimension | Across Corners Dimensions | Installation Torque (Nm) |
|---|---|---|---|---|---|---|
| 781EM2 | M20 x 1.5 | 15.0 | 17.0 | 30.0 | 33.0 | 7 |
| 781EM3 | M25 x 1.5 | 15.0 | 17.0 | 31.5 | 34.7 | 10 |
| 781ET1 | 1/2" NPT | 19.9 | 17.0 | 30.0 | 33.0 | 7 |
| 781ET2 | 3/4" NPT | 20.2 | 17.0 | 31.5 | 34.7 | 10 |
| Dimensions are displayed in millimetres unless otherwise stated | ||||||
NOTE: Marked with ATEX, IECEx and cCSAus certification details as standard. Please refer to Ordering Guide Tables for reference definitions, denoting material variants.
NOTE: Marked with ATEX, IECEx and cCSAus certification details as standard. Please refer to Ordering Guide Tables for reference definitions, denoting material variants.
| TECHNICAL DATA | ||||||||
|
|
||||||||
| cCSAus Approval Certificate No. | 1055233 |
| cCSAus Code of Protection Category | Ex e II, Class I, Zone 1, AEx e II; IP66; Enclosure Type 4X |
| cCSAus Compliance Standards | C22.2 No. 0.5-M1982, C22.2 No. 30-M1986, C22.2 No. 94-M1991,CAN/CSA E60079-0:07, CAN/CSA E60079-1:07,CAN/CSA E60079-7:02, UL Standard 50, Eleventh Edition, UL Standard 1203, Fourth Edition, UL 60079-0, Fourth Edition, UL 60079-1, Fifth Edition, UL 60079-7, First Edition |
| GOST R Certificate Number | POCC GB.HO06.B00207 |
| GOST R Code of Protection Category | Ex e II |
| GOST R Compliance Standards | ГOCT P 52350.0-2005, ГOCT P 52350.1-2005, ГOCT P 52350.7-2005, ГOCT MЭK 61241-1-1-99 |
| GOST GGTN Permit | PPC 00-40706 |
| GOST K Certificate Number | KZ 75000361 01 01 14761 |
| RoK Permit For Use Number | 19-02-UL-1957 |
| Lloyds Approval No. | 01/00172 |
| DNV Approval No. | E-10496 |
| ABS Approval No. | 01-LD234401C/1-PDA |
| INMETRO Approval Certificate Number. | AEX-13104-U |
| INMETRO Code of Protection Category | BR-Ex e II |
| INMETRO Compliance Standards | ABNT NBR IEC 60079-0:2006, IEC 60079-1:2007 e IEC 60079-2007:2001 |
| RETIE Approval Number | 03866 |
| Type | 781 |
| Design Specification | BS 6121:Part 1:1989 |
| ATEX Certification Detail | SIRA01ATEX1284U |
| ATEX Code of Protection Category | ATEX |
| ATEX Compliance Standards | EN 60079-0, EN 60079-1, EN 60079-7, EN 50281-1-1 |
| IEC Ex Certification Detail | IEC Ex SIR07.0054U |
| IEC Ex Code of Protection Category | Ex e II, Ex tD A21 IP6X |
| IEC Ex Compliance Standards | IEC 60079-0, IEC 60079-7, IEC 61241-0, IEC 61241-1 |
| Continuous Operating Temperature | -60°C to +60°C |
| Ingress Protection Rating | IP66 (when fitted in a bottom entry, perpendicular manner) |
| Material | Brass, Electroless Nickel Plated Brass, Aluminium, Stainless Steel |
Accessories included - Integral Entry Thread "O" Ring Seal, Castellated Locknut